Alliance Laundry Systems Clothes Dryer Drying Cabinet User Manual

Drying Tumblers  
Stacked 30 Pound Capacity  
Stacked 45 Pound Capacity  
Starting Serial No. 0602004144  
NOTA: Para bajar una  
copia de estas  
instrucciones en  
español, visite  
HIGH  
TEMP  
STA  
RT  
LOW  
TEMP  
MED  
TEMP  
NO  
HEAT  
25  
C
1
SELE  
TEMP  
2
INSE  
CT  
RT  
3
PUS  
COIN  
HIG  
H
TEM  
P
H
STAR  
T
STA  
RT  
LOW  
1
TEMP  
MED  
TE  
SELE  
TEMP  
2
INSE  
COIN  
CT  
MP  
RT  
3
PUS  
NO  
H
HEA  
T
STAR  
T
25  
C
T477C  
Keep These Instructions for Future Reference.  
(If this machine changes ownership, this manual must accompany machine.)  
Part No. 70304601R6  
February 2008  
 
Installation must conform with local codes or in the absence of local codes with:  
In the U.S.A., installation must conform to the latest edition of the American National Standard Z223.1/  
NFPA 54 “National Fuel Gas Code” and Standard ANSI/NFPA 70 “National Electric Code.”  
In Canada, installation must comply with Standards CSA-B149.1 or Natural Gas and Propane Installation  
Code and CSA C22.1, latest edition, Canadian Electric Code, Part I.  
In Australia, installation must comply with the Australian Gas Association Installation Code for Gas  
Burning Appliances and Equipment.  
WARNING  
MISE EN GARDE  
POUR VOTRE SÉCURITÉ, les informations  
de ce guide doivent être respectées afin de  
réduire les risques d’incendie, d’explosion  
ou d’éviter les dommages matériels,  
FOR YOUR SAFETY, the information in this  
manual must be followed to minimize the  
risk of fire or explosion or to prevent  
property damage, personal injury or death.  
W033  
personnels ou blessures mortelles.  
W033R3QU  
• Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
• WHAT TO DO IF YOU SMELL GAS:  
– Do not try to light any appliance.  
– Do not touch any electrical switch; do  
not use any phone in your building.  
– Clear the room, building or area of all  
occupants.  
– Immediately call your gas supplier from  
a neighbor’s phone. Follow the gas  
supplier’s instructions.  
– If you cannot reach your gas supplier,  
call the fire department.  
• Ne pas entreposer ou utiliser d’essence  
ou toutes autres vapeurs et liquides  
inflammables à proximité de cette  
machine ou de tout autre appareil.  
• QUE FAIRE EN CAS D’ODEUR DE GAZ :  
– Ne pas mettre d’appareil en marche.  
– Ne pas toucher aux interrupteurs  
électriques ; ne pas utiliser le  
téléphone des lieux.  
– Évacuer la pièce, le bâtiment ou la zone  
de tous les occupants.  
– Appeler immédiatement le fournisseur  
de gaz de la maison d’un voisin.  
Respecter les instructions  
communiquées par le fournisseur.  
– Si vous ne pouvez pas joindre le  
fournisseur de gaz, appeler le service  
d’incendie.  
• Installation and service must be  
performed by a qualified installer, service  
agency or the gas supplier.  
W052  
FOR YOUR SAFETY  
Linstallation et l’entretien doivent être  
effectués par un installateur, service  
d’entretien qualifiés ou par le fournisseur  
Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
de gaz.  
W052R5QU  
W053  
POUR VOTRE SÉCURITÉ  
The following information applies to the state of  
Massachusetts, USA.  
Ne pas entreposer ou utiliser d’essence ou  
toutes autres vapeurs et liquides  
inflammables à proximité de cette unité ou  
This appliance can only be installed by a  
Massachusetts licensed plumber or gas fitter.  
de tout autre appareil.  
W053R2QU  
This appliance must be installed with a 36  
inch (91 cm) long flexible gas connector.  
IMPORTANT: Information must be obtained from  
a local gas supplier on instructions to be followed if  
the user smells gas. These instructions must be  
posted in a prominent location. Step-by-step  
instructions of the above safety information must  
be posted in a prominent location near the tumbler  
for customer use.  
A "T-Handle" type gas shut-off valve must be  
installed in the gas supply line to this  
appliance.  
This appliance must not be installed in a  
bedroom or bathroom.  
70304601  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
1
Introduction.........................................................................................  
4
Table of  
Contents  
Safety Information..............................................................................  
6
Specifications and Dimensions...........................................................  
9
Installation........................................................................................... 15  
Exhaust Requirements ....................................................................... 24  
Gas Requirements............................................................................... 30  
Electrical Requirements..................................................................... 35  
© Copyright 2008, Alliance Laundry Systems LLC  
All rights reserved. No part of the contents of this book may be reproduced or transmitted in any form or by any  
means without the expressed written consent of the publisher.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
2
 
Steam Requirements........................................................................... 43  
Installing Steam Trap and Making Condensate  
Return Connections............................................................................ 44  
Single Drop Timer .............................................................................. 46  
Adjustments......................................................................................... 49  
Removing Tumbler from Service...................................................... 51  
70304601  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
3
 
Introduction  
Model Identification  
Information in this manual is applicable to these models:  
Gas  
Steam  
Electric  
CHD30STG2-CAT30L  
CHD30STG2-CAT30N  
CHD30STG2-CTT30L  
CHD30STG2-CTT30N  
CHD30STG2-CUT30L  
CHD30STG2-CUT30N  
DRST30G2-BAT30L  
DRST30G2-BAT30N  
DRST30G2-BTT30L  
DRST30G2-BTT30N  
DRST30G2-BUT30L  
DRST30G2-BUT30N  
HAT30L  
MTT30N  
NTT30N  
SAT30L  
SAT30N  
STT30D  
STT30L  
STT30N  
SUT30L  
SUT30N  
UAT30L  
UAT30N  
UTT30L  
UTT30N  
UUT30L  
UUT30N  
CHD30STS2-CTT30S  
CHD30STS2-CUT30S  
DRST30S2-BTT30S  
DRST30S2-BUT30S  
HTT30S  
HUT30S  
IPD30STS2-ITT30S  
STT30S  
CHD30STE2-CTT30E  
CHD30STE2-CUT30E  
DRST30E2-BTT30E  
DRST30E2-BUT30E  
HTT30E  
HUT30E  
IPD30STE2-ITT30E  
STT30E  
SUT30S  
UTT30S  
UUT30S  
SUT30E  
UTT30E  
UUT30E  
T30  
HAT30N  
HTT30D  
HTT30L  
HTT30N  
HUT30L  
HUT30N  
IPD30STG2-ITT30L  
IPD30STG2-ITT30N  
CTT45L  
CTT45N  
HTT45L  
HTT45N  
ITT45L  
ITT45N  
MTT45N  
NTT45N  
STT45L  
STT45N  
UTT45L  
UTT45N  
Not Applicable  
Not Applicable  
T45  
Includes models with control suffixes:  
3O– DX4 OPL  
BY– basic electronic, prep for card  
NC– NetMaster coin  
SD– single drop  
3V– DX4 vended  
SX– single drop, prep for coin  
ZC– NetMaster network coin  
3X– DX4 prep for coin  
BC– basic electronic, coin  
BL– basic electronic, central pay  
BX– basic electronic, prep for coin  
NR– NetMaster card  
NX– NetMaster, prep for coin  
NY– NetMaster, prep for card  
QT– dual digital timer  
ZR– NetMaster network card  
ZX– NetMaster network, prep for coin  
ZY– NetMaster network, prep for card  
Customer Service  
Wiring Diagram  
If literature or replacement parts are required, contact  
the source from which the machine was purchased or  
contact Alliance Laundry Systems at (920) 748-3950  
for the name and address of the nearest authorized  
parts distributor.  
The wiring diagram is located in the upper junction or  
upper contactor box.  
The wiring diagram part number is located in the  
lower portion of the electrical data on the serial plate.  
For technical assistance, call (920) 748-3121.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
4
         
Introduction  
Serial Plate Location  
When calling or writing for information about your  
product, be sure to mention model and serial numbers.  
Model and serial numbers are found on serial plate on  
the rear of machine and inside door.  
1
TMB1974N  
1
Serial Plate  
Conversion Table  
To Obtain Multiply  
kCal  
Multiply  
By  
By  
0.06895  
0.070  
0.454  
33,479  
34.5  
To Obtain  
Btu  
Btu  
Inch  
0.252  
1055  
25.4  
Pounds/sq. inch  
Pounds/sq. inch  
Pounds (lbs.)  
Boiler Horsepower  
Boiler Horsepower  
CFM  
Bars  
Joules  
kg/sq. cm  
Kilograms  
Btu/hr.  
Millimeters  
Pounds/sq. inch  
kPa  
Inches W.C.  
Inches W.C.  
0.036  
0.249  
6.895  
28.32  
lbs. steam/hr.  
liters/second  
Btu/hr.  
2
lb/inch (psi)  
kPa  
0.471  
3414  
3
ft  
Liters  
kW  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
5
 
 
Safety Information  
Explanation of Safety Messages  
WARNING  
Precautionary statements (“DANGER,” “WARNING,”  
and “CAUTION”), followed by specific instructions,  
are found in this manual and on machine decals. These  
precautions are intended for the personal safety of the  
operator, user, servicer, and those maintaining the  
machine.  
Failure to install, maintain, and/or operate  
this machine according to manufacturer’s  
instructions may result in conditions which  
can produce serious injury, death and/or  
property damage.  
W051R1  
DANGER  
NOTE: The WARNING and IMPORTANT  
instructions appearing in this manual are not  
meant to cover all possible conditions and  
situations that may occur. It must be understood  
that common sense, caution and carefulness are  
factors which CANNOT be built into this tumbler.  
These factors MUST BE supplied by the person(s)  
installing, maintaining or operating the tumbler.  
Indicates an imminently hazardous  
situation that, if not avoided, will cause  
severe personal injury or death.  
WARNING  
Indicates a hazardous situation that, if not  
avoided, could cause severe personal  
injury or death.  
Always contact your dealer, distributor, service agent  
or the manufacturer on any problems or conditions you  
do not understand.  
CAUTION  
Indicates a hazardous situation that, if not  
avoided, may cause minor or moderate  
personal injury or property damage.  
Additional precautionary statements (“IMPORTANT”  
and “NOTE”) are followed by specific instructions.  
IMPORTANT: The word “IMPORTANT” is used  
to inform the reader of specific procedures where  
minor machine damage will occur if the procedure  
is not followed.  
NOTE: The word “NOTE” is used to communicate  
installation, operation, maintenance or servicing  
information that is important but not hazard  
related.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
6
   
Safety Information  
14. The interior of the tumbler and the exhaust duct  
should be cleaned periodically by qualified  
service personnel.  
Important Safety Instructions  
Save These Instructions  
15. If not installed, operated and maintained in  
accordance with the manufacturer’s instructions  
or if there is damage to or mishandling of this  
product’s components, use of this product could  
expose you to substances in the fuel or from fuel  
combustion which can cause death or serious  
illness and which are known to the State of  
California to cause cancer, birth defects or other  
reproductive harm.  
WARNING  
Hazardous Voltage. Can cause shock, burn  
or cause death. Allow machine power to  
remain off for two minutes prior to working  
in and around AC inverter drive.  
W359  
1. Read all instructions before using the tumbler.  
16. Tumbler will not operate with the loading door  
open. DO NOT bypass the door safety switch to  
permit the tumbler to operate with the door open.  
The tumbler will stop tumbling when the door is  
opened. Do not use the tumbler if it does not stop  
tumbling when the door is opened or starts  
tumbling without pressing or turning the START  
mechanism. Remove the tumbler from use and  
call for service.  
2. Refer to the GROUNDING INSTRUCTIONS  
for the proper grounding of the tumbler.  
3. Do not dry articles that have been previously  
cleaned in, washed in, soaked in, or spotted with  
gasoline, dry cleaning solvents, other flammable  
or explosive substances as they give off vapors  
that could ignite or explode.  
4. Do not allow children on or in the tumbler. This  
appliance is not intended for use by young  
children or infirm persons without supervision.  
Young children should be supervised to ensure  
that they do not play with the appliance.  
17. Tumbler will not operate with lint panel open.  
DO NOT bypass lint panel safety switch to  
permit the tumbler to operate with the lint panel  
open.  
5. Before the tumbler is removed from service or  
discarded, remove the door to the drying  
compartment and the door to the lint  
compartment.  
18. Do not put articles soiled with vegetable or cooking  
oil in the tumbler, as these oils may not be  
removed during washing. Due to the remaining  
oil, the fabric may catch on fire by itself.  
6. Do not reach into the tumbler if the cylinder is  
revolving.  
19. To reduce the risk of fire, DO NOT put clothes  
which have traces of any flammable substances  
such as machine oil, flammable chemicals,  
thinner, etc. or anything containing wax or  
chemicals such as in mops and cleaning cloths, or  
anything dry-cleaned at home with dry-cleaning  
solvent in the tumbler.  
7. Do not install or store the tumbler where it will  
be exposed to water and/or weather.  
8. Do not tamper with the controls.  
9. Do not repair or replace any part of the tumbler,  
or attempt any servicing unless specifically  
recommended in the user-maintenance  
instructions or in published user-repair  
instructions that you understand and have the  
skills to carry out.  
20. Use the tumbler only for its intended purpose,  
drying fabrics.  
21. ALWAYS disconnect and lockout the electrical  
power to the tumbler before servicing. Disconnect  
power by shutting off appropriate breaker or fuse.  
10. Do not use fabric softeners or products to  
eliminate static unless recommended by the  
manufacturer of the fabric softener or product.  
22. Install this tumbler according to the  
INSTALLATION INSTRUCTIONS. All  
connections for electrical power, grounding, and  
gas supply must comply with local codes and be  
made by licensed personnel when required.  
11. To reduce the risk of fire, DO NOT DRY plastics  
or articles containing foam rubber or similarly  
textured rubberlike materials.  
12. Always clean the lint filter daily.  
13. Keep area around the exhaust opening and  
adjacent surrounding area free from the  
accumulation of lint, dust and dirt.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
7
 
Safety Information  
23. Remove laundry immediately after tumbler stops.  
29. DO NOT bypass any safety devices.  
24. Always read and follow manufacturer’s  
instructions on packages of laundry and cleaning  
aids. Heed all warnings or precautions. To reduce  
the risk of poisoning or chemical burns, keep  
them out of reach of children at all times  
(preferably in a locked cabinet).  
30. Solvent vapors from dry-cleaning machines  
create acids when drawn through the heater of the  
drying unit. These acids are corrosive to the  
tumbler as well as to the laundry load being  
dried. Be sure make-up air is free of solvent  
vapors.  
25. Do not tumble fiberglass curtains and draperies  
unless the label says it can be done. If they are  
dried, wipe out the cylinder with a damp cloth to  
remove particles of fiberglass.  
31. Failure to install, maintain, and/or operate this  
machine according to the manufacturer’s  
instructions may result in conditions which can  
produce bodily injury and/or property damage.  
26. Always follow the fabric care instructions  
supplied by the garment manufacturer.  
WARNING  
To reduce the risk of serious injury, install  
lockable door(s) to prevent public access  
27. Never operate the tumbler with any guards and/or  
panels removed.  
to rear of tumblers.  
28. DO NOT operate the tumbler if it is smoking,  
W055  
grinding, has missing or broken parts.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
8
Specifications and Dimensions  
Specifications  
T30  
T45  
66 dBA  
67 dBA  
Noise level measured during operation at operator  
position of 3.3 feet (1 meter) in front of machine and  
5.2 feet (1.6 meters) from floor.  
544  
(247)  
673  
(305)  
Net Weight (approximate):  
Pounds (kg)  
30 x 26  
(762 x 660)  
33 x 30  
(838 x 762)  
Cylinder Size:  
Inches (mm)  
2 x 30  
(2 x 13.6)  
2 x 45  
(2 x 20.5)  
Cylinder Capacity (dry weight)  
Pounds (kg)  
1/4  
1/4  
1/2  
1/2  
Drive Motor Horsepower**  
Fan Motor Horsepower**  
50 Hertz  
340  
(160)  
N/A  
Maximum Airflow per Pocket**:  
C.F.M. (l/sec)  
60 Hertz  
50 Hertz  
60 Hertz  
400  
(189)  
600  
(283)  
0.8  
(2.0)  
N/A  
Maximum Static Back Pressure*:  
Inches W.C. (mbar)  
0.9  
0.9  
(2.3)  
(2.3)  
Gas Models  
1/2 in. NPT  
1/2 in. NPT  
Gas Connection  
73,000  
(21.4, 77)  
95,000  
(27.8, 100.2)  
Gas Burner Rating**:  
Btu/hr (kW, Mj/hr)  
Electric Models  
Steam Models  
21 kW  
N/A  
Heating Element Rating**:  
Steam Connection  
3/4 in. NPT  
N/A  
N/A  
3.2  
(111,000)  
Steam Coil Rating at 100 psig**:  
Boiler Horsepower (Btu/hr)  
2.2  
(74,000)  
N/A  
Steam Coil Rating at 15 psig**:  
Boiler Horsepower (Btu/hr)  
* with both pockets running  
** for each pocket  
N/A = Not Applicable  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
9
 
 
Specifications and Dimensions  
Cabinet Dimensions  
J
A
B
C
D
E
F
H
I
G
TMB2230N  
Models  
T30  
A
B
C
D
E
28 in.  
(711 mm)  
48 in.  
(1219 mm)  
44 in.  
(1118 mm)  
11 in.  
(279 mm)  
10 in.  
(254 mm)  
31.88 in.  
(810 mm)  
49 in.  
(1245 mm)  
9 in.  
(229 mm)  
N/A  
N/A  
T45  
Models  
T30  
F
G
H
I
J
25.02 in.  
(636 mm)  
42.76 in.  
(1086 mm)  
27.38 in.  
(695 mm)  
31.5 in.  
(800 mm)  
76.25 in.  
(1937 mm)  
29.37 in.  
(746 mm)  
48.62 in.  
(1235 mm)  
30.50 in.  
(775 mm)  
34.5 in.  
(876 mm)  
81.25 in.  
(2063.75 mm)  
T45  
N/A = Not Applicable  
NOTE: To meet ADA compliance, install a 4 inch  
(102 mm) riser on T30 models only.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
10  
 
 
Specifications and Dimensions  
Exhaust Outlet Locations  
A
B
C
TMB1969N  
Rear Exhaust  
Models  
Diameter  
A
B
C
Elliptical  
T30  
36.54 in.  
(928 mm)  
4.25 in.  
(108 mm)  
62.42 in.  
(1585 mm)  
Fits 8 in. (203 mm)  
Elliptical  
T45  
40.88 in.  
(1038 mm)  
4.75 in.  
(121 mm)  
66.00 in.  
(1676 mm)  
Fits 10 in. (254 mm)  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
11  
 
 
Specifications and Dimensions  
Gas Connection Locations  
C
B
1
A
TMB1970N  
1
1/2 in. NPT  
Gas Connection  
B
Models  
A
C
Non-CE and  
75.20 in.  
1.74 in.  
36.84 in.  
Non-Australian  
(1910 mm)  
(44 mm)  
(936 mm)  
T30  
CE and  
75.28 in.  
2.5 in.  
30.60 in.  
Australian  
(1912 mm)  
(64 mm)  
(777 mm)  
78.75 in.  
(2000 mm)  
4.12 in.  
(105 mm)  
42.88 in.  
(1089 mm)  
T45  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
12  
 
 
Specifications and Dimensions  
Electrical Connection Locations  
B
E
A
D
C
GAS AND STEAM  
ELECTRIC  
TMB1971N  
Electric Service  
C
Models  
T30  
Gas and Steam Models  
Electric Models  
A
B
D
E
59 in.  
(1498 mm)  
1.75 in.  
(44 mm)  
35.63 in.  
(905 mm)  
73.21 in.  
(1859 mm)  
2.28 in.  
(58 mm)  
62.5 in.  
(1588 mm)  
1.75 in.  
(44 mm)  
N/A  
N/A  
N/A  
T45  
N/A = Not Applicable  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
13  
 
 
Specifications and Dimensions  
Steam Connection Locations  
C
D
A
B
A
B
TMB1972N  
Inlet  
Outlet  
Models  
A
C
B
D
73.93 in.  
6.29 in.  
62.71 in.  
2.39 in.  
T30  
(Upper)  
(1877 mm)  
(160 mm)  
(1592 mm)  
(61 mm)  
36.35 in.  
6.29 in.  
25.13 in.  
2.39 in.  
T30  
(Lower)  
(923 mm)  
(160 mm)  
(638 mm)  
(61 mm)  
NOTE: All connections use 3/4 inch NPT pipe.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
14  
 
 
Installation  
Pre-Installation Inspection  
Location Requirements  
Upon delivery, visually inspect the crate, carton and  
parts for any visible shipping damage. If the crate,  
carton, or cover is damaged or signs of possible  
damage are evident, have the carrier note the condition  
on the shipping papers before the shipping receipt is  
signed, or advise the carrier of the condition as soon as  
it is discovered.  
The tumbler must be installed on a level floor. Floor  
covering materials such as carpeting or tile should be  
removed.  
To assure compliance, consult local building code  
requirements. The tumbler must not be installed or  
stored in an area where it will be exposed to water  
and/or weather.  
Remove the crate and protective cover as soon as  
possible and check the items listed on the packing list.  
Advise the carrier of any damaged or missing articles  
as soon as possible. A written claim should be filed  
with the carrier immediately if articles are damaged or  
missing.  
IMPORTANT: DO NOT block the airflow at the  
rear of the tumbler with laundry or other articles.  
Doing so would prevent adequate air supply to the  
combustion chamber of the tumbler.  
A typical tumbler enclosure is shown in Figure 1. Note  
that the enclosure touches the tumbler top and side  
panels. Also, note the minimum and maximum  
dimensions. Local codes and ordinances must be  
complied with.  
IMPORTANT: Warranty is void unless tumbler is  
installed according to instructions in this manual.  
Installation should comply with minimum  
specifications and requirements detailed herein,  
and with applicable local gas fitting regulations,  
municipal building codes, water supply regulations,  
electrical wiring regulations, and any other  
relevant statutory regulations. Due to varied  
requirements, applicable local codes should be  
thoroughly understood and all pre-installation  
work arranged for accordingly.  
WARNING  
To reduce the risk of serious injury, install  
lockable door(s) to prevent public access to  
rear of tumblers.  
W055  
IMPORTANT: Install tumblers with sufficient  
clearance for servicing and operation. Refer to  
Material Required (Obtain Locally)  
One fused disconnect switch or circuit  
breaker.  
All Models  
IMPORTANT: Keep tumbler area clear and free  
from combustible materials, gasoline and other  
flammable vapors and liquids.  
One gas shut-off valve for gas service  
Gas Models  
line to each tumbler.  
One steam shut-off valve for steam  
service line to be connected upstream of  
solenoid steam valve.  
Steam  
Models  
Steam shut-off valve for each condensate  
return line.  
Flexible steam hoses with a 125 psig  
(pounds per square inch gauge)  
(8.78 kg/sq. cm) working pressure for  
connecting steam coils. Refer to  
Figure 14 for sizing and connection  
configurations.  
Steam trap for steam coil outlet to  
condensate return line.  
Optional – Vacuum breaker for  
condensate return line.  
Table 1  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
15  
     
Installation  
WARNING  
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible  
construction must conform to the minimum clearances.  
W056  
1
3
4
2
5
6
7
TMB2110N  
TMB2110N  
NOTE: Shaded areas indicate adjacent structure.  
1
2
0.5 in. (13 mm) recommended between machines for removal or installation.  
Allow 2 – 4 in. (51 – 102 mm) opening at top of machine to aid in removal or installation. A removable trim piece  
may be used to conceal the opening; zero clearance allowed for trim.  
4 in. (102 mm) Maximum Header Thickness  
3
4
5
6
12 in. (305 mm) Minimum Clearance  
24 in. (610 mm) Minimum, 36 in. (914 mm) recommended for maintenance purposes.  
Provision for Make-Up Air: Minimum 1.5 square feet T30 models, minimum 2 square feet T45 models. Location  
for reference only. May be anywhere behind tumbler.  
7
0.25 in. (6 mm) recommended for removal or installation purposes, zero clearance allowed.  
Figure 1  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
16  
 
 
Installation  
The stacked tumbler has a fifth leveling leg which is  
shipped in the up position. The fifth leveling leg  
MUST BE installed properly on the lower left side of  
the blower housing to stabilize the tumbler. Refer to  
Position and Level the Tumbler  
Unscrew the four shipping bolts (one at each corner).  
Remove tumbler from skid carefully to avoid putting  
pressure on the lower blower housing or motor  
assembly.  
After leveling with the four cabinet leveling legs,  
lower the fifth leveling leg so it contacts the floor, and  
then secure the screws.  
NOTE: Do not throw bolts away – they are the  
leveling legs.  
Remove four nuts from the literature package, and  
screw one fully on to each leveling leg.  
CAUTION  
Screw the four leveling legs (bolts) back into the level  
adjusting fittings from the bottom.  
The stacked drying tumbler has a 5th  
leveling leg on the blower housing. It is very  
important to properly adjust this leg. Unit is  
Slide tumbler to its permanent location. Adjust the  
leveling legs until the unit is level within 0.125 inch  
(32 mm) higher in the front. Refer to Figure 2.  
Tumbler must not rock. Lock leveling legs with nuts  
previously installed.  
back heavy and could rock or tip.  
W250  
NOTE: The front of the tumbler should be slightly  
higher than the rear (approximately 0.125 inch,  
3.18 mm). This will prevent the clothes, while  
tumbling, from wearing on the door glass gasket.  
IMPORTANT: Keep tumbler as close to floor as  
possible. The unit must rest firmly on floor so  
weight of tumbler is evenly distributed.  
1
T467I  
1
Fifth Leg  
Figure 3  
TMB1975N  
1
Leveling Leg  
Figure 2  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
17  
 
     
Installation  
IMPORTANT: The electronic ignition system will  
attempt to light the gas by sparking for the “trial  
for ignition” period. Refer to Table 2. If gas does  
not ignite within this period, the ignition control  
will go into a safety lockout and the valve will no  
longer open until the control is reset. It may be  
necessary to retry several times to bleed air from  
the gas lines. To reset, open and close the loading  
door and restart tumbler.  
Before Placing Tumbler into Service  
1. Remove or open all panels and check accessible  
bolts, nuts, screws, terminals and fittings for tightness.  
2. Replace all panels and guards.  
3. Remove and discard wire tie from the airflow  
switch so it can swing freely. Refer to Figure 4.  
IMPORTANT: Airflow switch operation may be  
affected by:  
If lockout condition persists, check that the manual  
gas shut-off valve is in the ON position and that the  
gas service is properly connected. If condition still  
persists, remove tumbler from service.  
Clogged lint screen.  
Failure to remove wire tie from rear of  
machine. Refer to Figure 4.  
8. Load the cylinder with a full load of clean rags  
and run to remove oil or dirt from cylinder.  
Lack of make-up air. Refer to Exhaust  
Requirements section.  
Obstruction in the exhaust duct. Refer to  
Exhaust Requirements section.  
WARNING  
Do not operate tumbler if airflow switch is  
faulty. An explosive gas mixture could  
collect in tumbler if airflow switch does not  
operate properly.  
1
W407  
Prepurge  
Time  
Trial for  
Ignition  
To Reset  
Lockout  
Models Location  
(seconds) (seconds) Condition:  
Press lighted  
CE and  
Australia  
reset button in  
rear contactor  
box  
18  
10  
T30  
Open loading  
door  
1-3  
1-3  
10  
10  
All others  
TMB2104N  
Open loading  
door  
TMB2104N  
T45  
1
Wire Tie  
Table 2  
Figure 4  
4. Turn on electrical supply to tumbler.  
5. Open the supply valve for gas or steam heated tumblers.  
6. After performing the previous checks, start the  
tumbler by pressing START. (Refer to the  
Operating Manual for detailed instructions.)  
Release the start button and open the loading  
door. The cylinder should stop rotating within  
seven seconds after the door is opened a  
maximum of 2 inches (51 mm). If it does not,  
adjust the loading door switch. Refer to  
Adjustments section.  
7. Gas tumblers: Start the tumbler and check the  
burner flame. Adjust the air inlet shutter as  
required. Refer to Adjustments section.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
18  
 
     
Installation  
Installing CE Gas Drying Tumblers  
WARNING  
9. Wipe out the cylinder using an all-purpose  
cleaner or detergent and water solution. Refer to  
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
• Close gas shut-off valve to gas tumbler  
before servicing.  
• Close steam valve to steam tumbler  
before servicing.  
• Never start the tumbler with any guards/  
panels removed.  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
tumbler is properly grounded.  
W002  
General Information  
This information is to be used when installing gas  
tumblers in countries, and/or on gases, different than  
the machine’s factory configuration. Tumblers are  
supplied from the factory for operation on Natural Gas  
1000 Btu/cu ft. (8914 kcal/m3), or L.P. Gas 2500 Btu/  
cu ft. (22,250 kcal/m3) in the countries of GB/IE/PT/  
ES/IT/GR/LU/CH. To install machines in any other  
country, or on any other gas, requires some level of  
modification.  
T452I  
Figure 5  
If the tumbler does not meet ANY of the listed  
requirements, remove tumbler from use. Refer to  
Removing Tumbler from Service section  
Required for CE Models Only  
Once machine is installed, please be sure to complete  
the following items:  
Burner orifices, stickers, block-open kits, regulator  
springs and other parts needed for conversions are to  
be ordered separately.  
Review and verify machine operation with  
customer.  
Models are built in two different configurations:  
Leave all literature and a signed Declaration of  
Regulated Natural Gas – Burner orifice is sized  
for Natural Gas, second family, group H (E) at  
20 mbar inlet pressure. Regulator/governor is  
operational. Gas valve CAN be field-converted to  
a non-regulating type.  
Conformity with customer.  
Review machine warranty information with  
customer.  
Apply warning sticker on front panel of machine,  
in language appropriate to country of sale  
(included in literature packet).  
Unregulated L.P. (Liquefied Petroleum) Gas –  
Burner orifice is sized for L.P., third family,  
group 3+ at 28.37 mbar inlet pressure. Regulator/  
governor is blocked open. Gas valve CANNOT  
be field-converted to a regulating type.  
Serial plates supplied from the factory are configured  
for the countries of GB/IE/PT/ES/IT/GR/LU/CH.  
These instructions pertain to the situations when the  
country of use or gas supply is different than that on  
the serial plate.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
19  
       
Installation  
Table 3 describes the different gases that are available  
in different CE countries, and how the machines need  
to be configured to operate with those gases. In the  
CE, there are Natural Gas configurations that do not  
allow for machine regulation, and L.P. Gas  
configurations that must be regulated. For L.P. Gas,  
third family B/P at 50 mbar, order regulated Natural  
Gas machines and convert according to Table 3.  
WARNING  
When converting the tumbler to a  
different gas or pressure, first verify that  
the supply inlet pressure is equipped with  
a pressure regulator (located ahead of the  
tumbler) that will maintain the gas supply  
at the inlet pressure specified.  
W430  
Basic Configuration  
1. Determine the necessary conversion operations to  
convert from the factory-supplied configuration  
to the desired configuration.  
2. Perform the conversions required so the machine  
is properly configured for the desired country and  
gas (refer to Specific Conversion Procedures  
section):  
SPECIFIED  
LOCAL INLET  
PRESSURE  
How to Convert Gas Valve from Regulated to  
Unregulated  
NOTE: Conversion from regulated to unregulated  
is only needed when regulated tumblers were  
ordered, but unregulated tumblers were needed, or  
if the gas supply type is changed at a later date.  
2
3
1
How to Change Burner Orifice Size  
How to Adjust Gas Valve Governor/Regulator  
T103K  
How to Change Regulator Spring, DE/AT  
Only  
1
2
3
Gas Shut-Off Valve (Ahead of pressure tap)  
Pressure Tap  
Gas Shut-Off Valve (Shown in closed position)  
3. If applicable, peel off the appropriate country  
sticker (included with machine) and apply it to  
the serial plate over the existing country  
information.  
Figure 6  
4. If applicable, peel off the appropriate conversion  
sticker (included with machine) and apply it to  
the data plate over the “ADJUSTED FOR ______  
GAS: ______” information.  
5. Commission tumbler for use.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
20  
 
   
Installation  
Gases and Configurations  
Burner  
Orifice  
Pressure,  
mbar  
Supply  
Group Pressure,  
mbar  
Burner  
Orifice  
Part No.  
Country  
Code  
Capacity/ Diameter,  
Gas Type  
Quantity  
Model  
mm  
Natural Gas  
L.P. Gas  
H
B/P  
E
20  
30  
8.0  
T30  
T45  
4.0  
4.6  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
M402992  
M411371  
DK/NO/  
SE/FI/CZ/  
EE/LV/LT/  
SI/SK  
No Governor  
8.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
20  
T30  
T45  
4.0  
4.6  
M402992  
M411371  
DE  
NL  
LL  
L
30  
No Governor  
11.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
25  
T30  
T45  
4.0  
4.6  
M402992  
M411371  
B/P  
E+  
+
30  
No Governor  
No Governor  
No Governor  
8.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
20 or 25  
28 or 37  
20  
T30  
T45  
3.3  
3.7  
M401021  
M401000  
BE/FR*  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
H
T30  
T45  
4.0  
4.6  
M402992  
M411371  
GB/IE/PT/  
ES/IT/GR/  
LU/CH  
+
28 or 37  
20  
No Governor  
8.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
H
T30  
T45  
4.0  
4.6  
M402992  
M411371  
AT  
CY/IS/MT  
HU  
B/P  
B/P  
H
30  
No Governor  
No Governor  
8.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
L.P. Gas  
30  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
25  
T30  
T45  
4.0  
4.6  
M402992  
M411371  
B/P  
H
30  
No Governor  
8.0  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Natural Gas  
L.P. Gas  
20  
T30  
T45  
4.0  
4.6  
M402992  
M411371  
PL  
3P  
37  
No Governor  
T30  
T45  
2.2  
2.5  
M401011  
M401007  
Burner orifice information at 0-2000 feet (0-600 meters)  
altitude.  
*
For Natural Gas, Group E+ applications, convert  
using L.P. Gas model and replace burner orifice(s).  
Table 3  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
21  
 
Installation  
2. Follow instructions in Conversion Kit, Part No.  
431485 (Johnson Part No. GM-70 CBP).  
Specific Conversion Procedures  
How to Convert Gas Valve from Regulated to  
Unregulated  
NOTE: This kit does not contain any burner  
orifices.  
NOTE: Conversion from regulated to unregulated  
is only needed when regulated tumblers were  
ordered, but regulated tumblers were needed.  
3. Change burner orifice size as required by the  
appropriate table according to How to Change  
Burner Orifice Size.  
Johnson GM7000 gas valve:  
4. Commission tumbler for use.  
1. Disconnect electrical power from tumbler. Close  
gas shut-off valve to tumbler. Refer to Figure 7.  
1
10  
9
2
8
7
3
6
4
5
TMB2135N  
1
2
3
4
Gas Shut-Off Valve Assembly (closed position)  
Gas Valve  
Burner Orifice  
Regulator Adjusting Housing and Gasket  
(Regulated version shown)  
Gas Valve Bracket  
6
7
8
Required Burner Orifice Pressure  
Manometer  
Hose - Connect Over Loosened Slotted  
Pressure Tap Screw in Bottom of Gas Valve  
Spud Holder  
9
10  
5
Outlet Pressure Tap  
Figure 7  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
22  
 
   
Installation  
How to Change Burner Orifice Size  
1. Disconnect electrical power from tumbler. Close  
gas shut-off valve to tumbler. Refer to Figure 6.  
2. For Johnson GM7000 gas valve:  
Remove burner orifice(s) from the spud holder.  
Refer to Figure 7.  
3. Install the new, correct burner orifices. Refer to  
Figure 8. Torque each to 9 – 10 Nm.  
4. Commission tumbler for use.  
NOTE: Blank burner orifices are available as Part  
No. M400995.  
How to Adjust Gas Valve Governor/Regulator  
1. Check gas burner orifice (manifold) pressure as  
follows. Refer to Figure 7.  
2. Loosen screw plug inside pressure tap located on  
underside of valve.  
3. Connect a “U”- tube manometer (or similar  
pressure gauge) to the tap.  
4. Start tumbler and note pressure once flame is  
burning. Remove regulator cap and adjust  
regulator screw until the injector pressure per  
applicable table is achieved. Replace regulator  
cap and close needle valve (pressure tap).  
5. Commission tumbler for use.  
1
BURNER  
ORIFICE  
TMB2015N  
1
Size Stamped on Burner Orifice  
Figure 8  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
23  
 
Exhaust Requirements  
Venting  
WARNING  
For maximum efficiency and minimum lint  
accumulation, tumbler air must be exhausted to the  
outdoors by the shortest possible route.  
A drying tumbler produces combustible  
lint. To reduce the risk of fire, the tumbler  
must be exhausted to the outdoors.  
Proper sized exhaust ducts are essential for proper  
operation. All elbows should be sweep type. Exhaust  
ducts must be assembled so the interior surfaces are  
smooth, so the joints do not permit the accumulation  
of lint. DO NOT use plastic or thin foil flexible ducts.  
Use exhaust ducts made of sheet metal or other non-  
combustible material. Use duct tape or pop-rivets on  
all seams and joints.  
W057  
To reduce the risk of fire and  
accumulation of combustible gases, DO  
NOT exhaust tumbler air into a window  
well, gas vent, chimney or enclosed,  
unventilated area such as an attic wall,  
ceiling, crawl space under a building, or  
concealed space of a building.  
W059  
Verify that old ducts are thoroughly cleaned out before  
installing new tumbler(s).  
Layout  
Whenever possible, install tumblers along an outside  
wall where duct length can be kept to a minimum, and  
make-up air can be easily accessed. Elbows and long  
vents tend to increase drying time. Construction must  
not block the airflow at the rear of the tumbler. Doing  
so would prevent adequate air supply to the tumbler’s  
combustion chamber.  
WARNING  
Improperly sized or assembled ductwork  
causes excess back pressure which  
results in slow drying, lint collecting in  
the duct, lint blowing back into the room,  
and increased fire hazard.  
W355  
Make-Up Air  
NOTE: Exhaust ducts must be constructed of sheet  
metal or other noncombustible material. Such  
ducts must be equivalent in strength and corrosion  
resistance to ducts made of galvanized sheet steel  
not less than 0.0195 inches (0.495 mm) thick. Local  
codes may require additional thickness.  
A tumbler is forced air exhausted and requires provisions  
for make-up air to replace air exhausted by the tumbler.  
IMPORTANT: Do not obstruct the flow of  
combustion and ventilation air.  
Make-up air openings should be as close to the  
tumbler(s) as possible.  
Where the exhaust duct pierces a combustible wall or  
ceiling the opening must be sized per local codes. The  
space around the duct may be sealed with  
The required make-up air opening to the outside for  
each tumbler (includes both pockets) is:  
220 square inches (1418 sq. cm) for T30 models  
288 square inches (1856 sq. cm) for T45 models  
IMPORTANT: For best performance provide an  
individual exhaust duct for each tumbler. Do not  
install a hot water heater in a room containing  
tumblers. It is better to have the water heater in a  
separate room with a separate air inlet.  
Make-up air openings with louvers will restrict  
airflow. The opening must be increased to compensate  
for area taken up by louvers.  
Make-up air openings for a room containing  
tumbler(s) and/or gas fired hot water heater or other  
gravity vented appliances must be increased  
sufficiently to prevent downdrafts in any of the vents  
when all tumblers are in operation. Do not locate  
gravity vented appliances in the same room as  
tumblers. If it is necessary to duct make-up air to the  
tumbler(s), increase the area of the ductwork by 25%  
to compensate for any restriction in air movement.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
24  
       
Exhaust Requirements  
Individual Venting  
Duct  
Diameter  
Equivalent Length of  
Straight Duct  
For maximum efficiency and performance, it is preferred  
to exhaust tumbler(s) individually to the outdoors.  
10 in. (254 mm)  
12 in. (305 mm)  
14 in. (355.6 mm)  
16 in. (406.4 mm)  
18 in. (457.2 mm)  
One 90° elbow = 11.6 ft. (3.5 m)  
One 90° elbow = 14 ft. (4.3 m)  
One 90° elbow = 16 ft. (4.9 m)  
One 90° elbow = 18.7 ft. (5.7 m)  
One 90° elbow = 21 ft. (6.4 m)  
IMPORTANT: At no point may the cross sectional  
area of installed venting be less than the cross  
sectional area of the exhaust outlet of the tumbler.  
The exhaust duct must be designed so the static back  
pressure measured 12 inches (305 mm) from the  
exhaust outlet does not exceed the maximum  
allowable pressure specified on the installation sticker  
on the rear of the tumbler.  
Equivalent Length (feet) = 1.17 x Duct Diameter (inches)  
Table 4  
Example: A 12 inch (305 mm) diameter duct’s  
equivalent length of 14 feet (4.3 m) of duct and two  
90° elbows is:  
NOTE: Static back pressure must be measured  
with both pockets running.  
Equivalent Length = 14 feet + (2) 90° elbows  
= 14 feet + 14 feet + 14 feet  
The maximum allowable length venting of the same  
diameter as the exhaust thimble is 14 feet (4.3 m) and  
two 90° elbows or equivalent. If the equivalent length  
of a duct required for an installation exceeds the maximum  
allowable equivalent length, the diameter of a round duct  
must be increased by 10% for each additional 20 feet  
(6.1 m). Cross section area of a rectangular duct must  
be increased by 20% for each additional 20 feet (6.1 m).  
Refer to Table 4 to determine equivalent venting.  
= 42 feet (12.8 m)  
With the tumbler in operation, and both pockets  
running, airflow at any point in the duct should be at  
least 1200 feet per minute (366 meters per meter) to  
ensure that lint remains airborne. If 1200 feet per  
minute cannot be maintained, schedule monthly  
inspections and cleaning of the ductwork.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
25  
   
Exhaust Requirements  
3
4
2
1
5
TMB2103N  
1
2
3
4
5
Removable strip of panel in framing wall to permit removal of tumbler from framing wall  
Partition or bulkhead  
Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)  
2 in. (51 mm) minimum clearance on both sides of duct  
Exhaust airflow – maximum length of duct: 14 ft. (4.3 m)  
Figure 9  
NOTE: Do not install wire mesh or screen in  
exhaust duct opening to avoid lint build-up or  
impacting proper discharge of air from tumblers.  
NOTE: Where exhaust duct pierces a combustible  
wall or ceiling, the opening must be sized per local  
codes.  
NOTE: Inside of duct must be smooth. Do not use  
sheet metal screws to join sections.  
Consult your local building code for regulations which  
may also apply.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
26  
 
Exhaust Requirements  
NOTE: Never connect a tumbler duct at a 90° angle  
to the collector duct. Refer to Figure 10. Doing so  
will cause excessive back pressure, resulting in poor  
performance. Never connect two tumbler exhaust  
ducts directly across from each other at the point of  
entry to the collector duct.  
Manifold Venting  
While it is preferable to exhaust tumblers individually  
to the outdoors, a main collector duct may be used if it  
is sized according to Figure 11. This illustration  
indicates minimum diameters, and should be increased  
if the collector length exceeds 14 feet (4.3 m) and two  
90° elbows. The diameter of a round duct must be  
increased by 10% for each additional 20 feet (6.1 m).  
Cross sectional area of a rectangular or square duct must  
be increased 20% for each additional 20 feet (6.1 m).  
Refer to Table 5 to determine equivalent ducting  
sizing. The collector duct may be rectangular or square  
in cross section, as long as the area is not reduced.  
Provisions MUST be made for lint removal and  
cleaning of the collector duct.  
With the tumbler in operation, and both pockets  
running, airflow at any point in the duct should be at  
least 1200 feet per minute (366 meters per meter) to  
ensure that lint remains airborne. If 1200 feet per  
minute cannot be maintained, schedule monthly  
inspections and cleaning of the ductwork.  
The vent collector system must be designed so the  
static back pressure measured 12 inches (305 mm)  
from the exhaust outlet does not exceed the maximum  
allowable pressure specified on the installation sticker  
on the rear of tumbler. Static back pressure must be  
measured with all tumblers vented into the collector  
operating.  
T438I  
Figure 10  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
27  
   
Exhaust Requirements  
1
2A  
L
K
J
I
H
G
F
D
C
B
A
E
3
ONE BATTERY SAME AS LARGEST STATION USED  
TMB2019N  
1
2B  
L
L
K
J
I
J
K
I
CONTINUE  
TO A  
CONTINUE  
TO A  
3
TWO BATTERIES  
TMB2018N  
1
NOTE: Where the exhaust duct pierces a  
combustible wall or ceiling, the opening  
MUST be sized per local codes.  
2A  
2B  
3
Outlet Duct Diameter for One Battery  
Outlet Duct Diameter for Two Batteries  
45° Typical  
Figure 11  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
28  
 
 
Exhaust Requirements  
T45  
T30  
Duct Station  
8 in. (203 mm) Duct  
10 in. (254 mm) Duct  
2A  
2B  
2A  
2B  
9 in. (229 mm)  
12 in. (305 mm)  
15 in. (381 mm)  
17 in. (432 mm)  
19 in. (483 mm)  
21 in. (533 mm)  
23 in. (584 mm)  
24 in. (610 mm)  
26 in. (660 mm)  
27 in. (686 mm)  
28 in. (711 mm)  
30 in. (762 mm)  
12 in. (305 mm)  
17 in. (432 mm)  
22 in. (559 mm)  
25 in. (635 mm)  
27 in. (686 mm)  
30 in. (762 mm)  
33 in. (838 mm)  
34 in. (864 mm)  
37 in. (940 mm)  
39 in. (991 mm)  
40 in. (1016 mm)  
43 in. (1092 mm)  
10 in. (254 mm)  
15 in. (381 mm)  
18 in. (457 mm)  
21 in. (533 mm)  
24 in. (610 mm)  
26 in. (660 mm)  
28 in. (711 mm)  
30 in. (762 mm)  
32 in. (813 mm)  
33 in. (838 mm)  
35 in. (889 mm)  
36 in. (914 mm)  
15 in. (381 mm)  
22 in. (559 mm)  
26 in. (660 mm)  
30 in. (762 mm)  
34 in. (864 mm)  
37 in. (940 mm)  
40 in. (1016 mm)  
43 in. (1092 mm)  
46 in. (1168 mm)  
47 in. (1194 mm)  
50 in. (1270 mm)  
51 in. (1295 mm)  
A
B
C
D
E
F
G
H
I
J
K
L
Table 5  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
29  
 
 
Gas Requirements  
The following must be furnished and installed by the  
customer for the gas service line to each tumbler.  
Refer to Figure 12.  
WARNING  
To reduce the risk of fire or explosion, DO  
NOT CONNECT THE GAS LINE TO THE  
TUMBLER IF THE GAS SERVICE IS NOT  
THE SAME AS THAT SPECIFIED ON THE  
TUMBLER SERIAL PLATE! It will first be  
necessary to convert the gas burner  
orifice and gas valve. Appropriate  
Sediment traps  
Shut-off valves  
Supply pressure taps  
It is important that equal pressure be maintained at all  
tumbler gas connections. This can best be done by  
installing a one inch (25 mm) pipe gas loop. Refer to  
conversion kits are available.  
W060  
IMPORTANT: Any product revisions or conversions  
must be made by the Manufacturer’s Authorized  
Dealers, Distributors or local service personnel.  
WARNING  
To reduce the risk of fire or explosion, if  
the tumbler is to be connected to  
Liquefied Petroleum (L.P.) gas, a vent to  
the outdoors must be provided in the  
room where the tumbler is installed.  
IMPORTANT: The tumbler must be isolated from  
the gas supply piping system by closing its  
individual manual shut-off valve during any  
pressure testing of the gas supply piping system at  
test pressure equal to or less than 0.5 psig  
(3.45 kPa, 34.5 mbar).  
W062  
NATURAL GAS line pressure must be maintained at  
6.5 water column inches (1.62 kPa) with no less than 5  
water column inches (1.24 kPa) and no more than 10.5  
water column inches (2.61 kPa), with all gas  
appliances running (tumblers, water heaters, space  
heaters, furnace, etc.). An in-line pressure regulator  
may be required if the line pressure exceeds 8 water  
column inches (2.0 kPa) with all gas appliances  
running.  
IMPORTANT: The tumbler and its manually  
operated appliance gas valve must be disconnected  
from the gas supply piping system during any  
pressure testing of that system at test pressures in  
excess of 0.5 psi (3.45 kPa, 34.5 mbar).  
IMPORTANT: The installation must comply with  
local codes or, in the absence of local codes:  
LIQUID PETROLEUM GAS (L.P.) line pressure must  
be maintained at 11 water column inches (2.74 kPa),  
with no less than 10 water column inches (2.49 kPa)  
and no more than 13 water column inches (3.23 kPa),  
with all gas appliances running (tumblers, water  
heaters, space heaters, furnace, etc.).  
with the latest edition of the “National Fuel  
Gas Code,” ANSI Z223.1/NFPA 54 in the  
U.S.A.,  
with CSA-B149.1 or Natural Gas and Propane  
Installation Code in Canada,  
and Australian Gas Association/Australian  
L.P. Gas Association requirements in  
Australia.  
For converting Non-CE models from Natural Gas to  
L. P. Gas:  
T30 – M4707P3  
T45 – M4880P3  
Obtain specific gas service pipe size from the gas  
supplier. Refer to Table 6 for general pipe size.  
CE GASES refers to Installing CE Gas Drying  
Tumblers sections, the above data does not apply to  
the CE.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
30  
 
Gas Requirements  
Turn on gas and check all pipe connections (internal  
and external) for gas leaks with a non-corrosive leak  
detection fluid. Purge air in gas service line by  
operating the tumblers in the drying mode. If burner  
does not light and unit goes into lockout, open and  
close the door and restart. Repeat these steps until  
burner ignites. Use pipe compound, resistant to  
actions of L.P. gas, on all pipe threads.  
2
3
1
4
5
8
7
WARNING  
Check all pipe connections, internal and  
external, for gas leaks using a non-  
corrosive leak detection fluid. To reduce  
the risk of explosion or fire, DO NOT USE  
AN OPEN FLAME TO CHECK FOR GAS  
LEAKS! Gas connections should be  
6
TMB2007N  
1
Gas Line to Tumbler  
Shut-Off Valve  
Gas Supply Piping System  
Gas “T” Fitting  
2
3
4
5
6
7
8
checked twice a year for leakage.  
W635  
6 in. (152 mm) Minimum Gas Pipe  
Gas Pipe Cap  
Sediment Trap  
Supply Pressure Tap  
Figure 12  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
31  
 
 
Gas Requirements  
Gas Supply Pipe Sizing and Looping  
1
3
2
12  
11  
9
10  
1
2
3
4
5
6
7
8
9
4
M
5
8
6
7
TMB2126N  
1
2
3
4
Gas Furnace (120,000 Btu/hr.)  
8
9
10  
11  
12  
25 ft. (7.6 m)  
Main Regulator  
Gas Meter  
Pressure Regulator (if required)  
T30 Tumblers (73,000 Btu/hr per pocket;  
146,000 total Btu/hr for machine)  
Gas Water Heaters (400,000 Btu/hr. each)  
Gas Space Heaters (70,000 Btu/hr. each)  
Sediment Traps, Supply Pressure Taps and  
Shut-off Valves. Refer To Figure 12.  
1 in. (25.4 mm) Gas Pipe Loop  
5
6
7
19 ft. (5.8 m)  
Minimum Pipe Size is 0.5 in. (12.7 mm)  
T45 Tumblers (95,000 Btu/hr per pocket;  
190,000 total Btu/hr for machine)  
SAMPLE CALCULATIONS:  
Equivalent length = Total length of main gas supply pipe to the far end of the tumblers.  
= 25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe  
= 44 ft. (13.4 m) Total Gas Line  
Total Btu/hr.  
= The sum of the Btu/hr. of all T30 tumblers being fed by the main gas supply pipe.  
= 9 x 73,000  
= 657,000 Btu/hr.  
Using Table 6, the main supply pipe diameter should be 2 in. (51 mm).  
IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers  
connected to single gas service. Other gas using appliances should be connected upstream from loop.  
Figure 13  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
32  
 
   
Gas Requirements  
Gas Pipe Size Required for 1000 Btu Natural Gas — 0.64 Specific Gravity  
at 7 ± 1.5 inches (17.4 ± 4 mbar, 1.74 ± 0.37 kPa) Water Column Pressure  
Equivalent Length  
25 feet  
(7.63 m)  
50 feet  
75 feet  
100 feet  
125 feet  
150 feet  
(45.75 m)  
Gas  
Appliances  
Total Btu/hr  
(15.25 m)  
(22.88 m)  
(30.50 m)  
(38.13 m)  
Based on 0.3 in. Water Column Pressure Drop for Length Given  
Sizes shown in inches (mm)  
100,000  
120,000  
140,000  
160,000  
180,000  
200,000  
300,000  
400,000  
500,000  
600,000  
700,000  
800,000  
900,000  
1,000,000  
1,100,000  
1,200,000  
1,300,000  
1,400,000  
1,500,000  
1,600,000  
1,700,000  
1,800,000  
1,900,000  
2,000,000  
2,200,000  
2,400,000  
2,600,000  
2,800,000  
3,000,000  
0.75 (19.05)  
0.75 (19.05)  
0.75 (19.05)  
0.75 (19.05)  
1 (25.40)  
0.75 (19.05)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
4 (101.60)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
For L.P. Gas, correct the total Btu/hr by multiplying it by 0.6. The answer is the equivalent Btu on the  
above chart.  
The installation must conform with local codes or, in the absence of local codes:  
with the latest edition of the “National Fuel Gas Code,ANSI Z223.1/NFPA 54 in the U.S.A.,  
with CSA-B149.1 or Natural Gas and Propane Installation Code in Canada,  
and Australian Gas Association/Australian L.P. Gas Association requirements in Australia.  
Table 6  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
33  
 
 
Gas Requirements  
High Altitude Burner Orifice Sizing  
For proper operation at altitudes above 2000 feet  
(610 meters), the gas burner orifice size must be  
reduced to ensure complete combustion. Refer to  
For CE models, consult local gas supplier.  
Altitude  
Burner Orifice  
New Rate  
(Btu/hr.)*  
Model  
T30  
Gas  
Part  
Number  
Feet  
Meters  
No. Inches mm Quantity  
Natural Gas 2001-4000  
4001-6000  
610-1220  
1221-1830  
1831-2440  
2441-3050  
610-1830  
22  
24  
26  
28  
42  
43  
44  
15  
17  
18  
20  
36  
37  
38  
40  
0.1570  
0.1520  
0.1470  
0.1405  
0.0935  
0.0890  
0.0860  
0.1800  
0.1730  
0.1695  
0.1610  
0.1065  
0.1040  
0.1015  
0.0980  
4.0  
3.9  
3.7  
3.6  
2.4  
2.3  
2.2  
4.6  
4.4  
4.3  
4.1  
2.7  
2.6  
2.6  
2.5  
M402996  
M402980  
M401000  
M401014  
M403017  
M406184  
M401011  
M411511  
M411374  
M402988  
M401002  
M402487  
M411375  
M411376  
M406361  
134,320  
122,640  
110,960  
99,280  
6001-8000  
8001-10,000  
2
L.P. Gas  
2001-6000  
6001-8000  
8001-10,000  
134,320  
110,960  
99,280  
1831-2440  
2441-3050  
610 – 1220  
Natural Gas 2001 – 4000  
183,000  
168,400  
155,000  
142,600  
183,000  
168,400  
155,000  
142,600  
T45  
4001 – 6000 1221 – 1830  
6001 – 8000 1831 – 2440  
8001 – 10000 2441 – 3050  
2
L.P. Gas  
2001 – 4000  
610 – 1220  
4001 – 6000 1221 – 1830  
6001 – 8000 1831 – 2440  
8001 – 10000 2441 – 3050  
* Btu/hr. derate of 4% per 1000 feet (305 meters) of altitude.  
Table 7  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
34  
 
   
Electrical Requirements  
This tumbler must be grounded. In the event of  
malfunction or breakdown, grounding will reduce the  
risk of electric shock by providing a path of least  
resistance for electric current. This tumbler must be  
connected to a grounded metal, permanent wiring  
system; or an equipment grounding conductor must be  
run with the circuit conductors and connected to the  
appropriate ground location.  
WARNING  
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
• Close gas shut-off valve to gas tumbler  
before servicing.  
Metal conduit and/or BX cable is not considered  
• Close steam valve to steam tumbler  
before servicing.  
ground.  
• Never start the tumbler with any guards/  
panels removed.  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
Connecting the Neutral from the electrical  
service box to the tumbler ground screw does not  
constitute a ground.  
A dedicated ground conduit (wire) must be  
connected between the electrical service box  
ground bar and tumbler ground screw.  
tumbler is properly grounded.  
W002  
WARNING  
To reduce the risk of electrical shock,  
de-energize the electrical circuit being  
connected to the tumbler before making  
any electrical connections. All electrical  
connections should be made by a  
qualified electrician. Never attempt to  
connect a live circuit.  
W409  
machine, if there is a “High Leg” or  
“Stinger Leg” it should be connected to  
CAUTION  
L3.  
Label all wires prior to disconnection  
when servicing controls. Wiring errors  
can cause improper and dangerous  
operation. Verify proper operation after  
W069  
Grounding Instructions  
servicing.  
NOTE: To ensure protection against shock, this  
tumbler MUST be electrically grounded in  
accordance with the local codes, or in the absence  
of local codes, with the latest edition of the National  
Electrical Code ANSI/NFPA No. 70. In Canada the  
electrical connections are to be made in accordance  
with CSA C22.1 latest edition Canadian Electrical  
Code, or local codes.  
W071  
For CE Models Only  
All manually operated models are factory-equipped  
with an emergency stop button on the front panel. If  
the emergency stop function is desired on coin-  
operated models, an external emergency stop button  
may be installed as specified on the machine wiring  
diagram.  
NOTE: Activation of the emergency stop button  
stops all machine control circuit functions, but  
DOES NOT remove all electrical power from  
machine.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
35  
     
Electrical Requirements  
Service/Ground Location  
Model  
Heat Source  
Ground and Terminal Block Locations  
Terminal Block  
Ground Screw  
5
4
3
2
1
70219001R2  
SECURE GROUND  
WIRETO  
GROUND SCREW  
T30/T45  
Non-CE  
Gas or Steam  
TMB2041N  
Ground Lug  
SECURE GROUND  
WIRE TO  
GROUND SCREW  
L1 L 2 L 
1L1  
13 NO 21 NC A1  
LC1D32  
13 NO 21 NC A1  
LC1D32  
POWER  
DISTRIBUTION  
BLOCK  
Power Distribution  
Block  
14 NO 22 NC A2  
14 NO 22 NC A2  
2T1  
4T2  
6T3  
2T1  
4T2  
6T3  
T30  
Non-CE  
Electric  
TMB2113N  
Power  
POWER DISCONNECT  
Disconnect  
A
B
1
1
2
3
4
5
6
7
8
CIRCUIT DIAGRAM  
SECURE GROUND  
WIRE TO  
GROUND SCREW  
GROUN
T30  
CE  
Gas or Steam  
Ground Screw  
TMB2114N  
L1 L 2 L 3  
PE  
M412096  
GROUND  
LUG  
Power Distribution  
Block  
L1  
POWER  
DISTRIBUTION  
BLOCK  
1
13 NO 21 NC A1  
LC1D32  
14 NO 22 NC A2  
2T1  
4T2  
6T3  
T30  
CE  
Ground Lug  
Electric  
TMB2115N  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
36  
 
 
Electrical Requirements  
If tumbler requires conversion for use on another  
service voltage, complete the steps detailed in the  
Conversion Instructions section prior to connecting  
service to machine.  
Connecting Electrical Service  
The following steps outline the procedure for  
connecting electrical service to the tumbler.  
3 Phase models – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of  
“single phasing” and causing premature  
failure of the motor(s).  
If tumbler does not require conversion or has been  
converted according to the Conversion Instructions  
section of this manual, continue with step 1.  
NOTE: The wiring diagram is located in the upper  
junction box or upper contactor box.  
Electrical service must be connected using the  
appropriate permanent rigid metal conduit  
system.  
1. For new service, install a circuit breaker or fused  
disconnect of proper voltage and current rating as  
close to each tumbler as possible.  
Service conductors must be copper only.  
2. Route service conduit from circuit breaker panel  
or disconnect panel to tumbler service connection  
box. Conduit routing should not obstruct access  
for maintenance or servicing. Refer to Service/  
Ground Location.  
For an existing service, determine your service voltage  
and conductor amperage. Carefully review the tumbler  
serial plate ratings and Electrical Requirements  
section of this manual. If service is inadequate it must  
be upgraded by a qualified electrical contractor. Never  
connect an improper or inadequate service to any  
machine.  
3. Pull conductors through conduit and attach to  
circuit breaker and ground connection. Secure  
service ground wire to the grounding screw or  
lug. Attach service conductors to appropriately  
labeled positions on the terminal block. Make  
sure all connections are secure.  
Configuring Your Tumbler for Other  
Service Voltages  
Several gas and steam tumbler models have been  
designed to be field convertible to other service  
voltages. Refer to Table 8 for these models:  
4. Check electrical service phase sequence (3 Phase  
models only) as follows:  
a. Energize the electrical service and  
Your tumbler can be  
If your Serial Plate  
momentarily start the tumbler. Check the  
direction of cylinder rotation. If the cylinder  
rotates clockwise as viewed from the front,  
the phase sequence is correct. If the cylinder  
rotates counterclockwise, proceed with step b.  
Models  
converted to the  
voltage is:  
following voltages:  
120 Volt/60 Hertz/  
1 Phase  
208-240 Volt/60 Hertz/  
1 Phase  
T30  
T30  
T30  
b. Disconnect power to machine, disconnect and  
reverse the L1 and L2 connections on the  
terminal block.  
200-220 Volt/60 Hertz/  
1 Phase  
100 Volt/60 Hertz/  
1 Phase  
200 Volt/50 Hertz/  
1 Phase  
100 Volt/50 Hertz/  
l Phase  
Electrical Connections  
All gas and steam tumblers require a single service  
connection to TB1 of the upper unit junction box only.  
The serial plate reflects current draw, breaker/fuse size  
and conductor amperage required for the entire  
machine.  
240 Volt/60 Hertz/  
3 Phase  
200-208 Volt/60 Hertz/  
3 Phase  
T30/  
T45  
380 Volt/50 Hertz/  
3 Phase  
400-415 Volt/50 Hertz/  
3 Phase  
T30  
Table 8  
All electric tumblers require separate service  
connections for each upper and lower unit. Serial Plate  
ratings reflect current draw, breaker/fuse size and  
conductor amperage required per unit.  
NOTE: Electric models are not field convertible  
and must be connected to service specified on serial  
plate.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
37  
       
Electrical Requirements  
Conversion Instructions  
If serial plate voltage is:  
Tumbler can be converted to the following voltages:  
120 Volt/60 Hertz/  
1 Phase  
208-240 Volt/60 Hertz/1 Phase Models:  
3W&G  
2W&G  
1. Prior to connecting service, locate the black/red wire which runs between  
terminal block and the motor relay or contactor. Refer to figure below.  
(T30 Models Only)  
120 V~ LOCATION  
(AS RECEIVED)  
L1  
208 or 240 V~  
LOCATION  
(AS CONVERTED)  
120 V-  
120 V-  
208 OR  
240 V-  
L2  
L3  
TO MOTOR RELAY  
OR CONTACTOR  
BLK/RED  
TERMINAL BLOCK  
T381I  
2. Disconnect the black/red lead from L1 of the terminal block and connect to  
L2 of the terminal block. Repeat steps 1 and 2 for upper and lower junction  
box areas.  
3. Sign and date conversion sticker located on back of tumbler.  
4. Follow the instructions covered in Connecting Electrical Service section.  
240 Volt/60 Hertz/  
3 Phase  
200-208 Volt/60 Hertz/3 Phase Models:  
3W&G  
3W&G  
1. Prior to connecting electric service, locate transformer configuration jumper  
in junction box area.  
2. Remove the 240 Volt jumper and replace it with the 208 Volt jumper located  
in the literature packet in cylinder.  
3. Repeat steps 1 and 2 for each upper and lower unit.  
4. Sign and date conversion sticker located on back of tumbler.  
5. Follow the instructions covered in Connecting Electrical Service section.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
38  
 
 
Electrical Requirements  
If serial plate voltage is:  
Tumbler can be converted to the following voltages:  
200-220 Volt/60 Hertz/  
1 Phase  
100 Volt/60 Hertz/1 Phase INTERNATIONAL Models:  
2W&G  
2W&G  
100 Volt/50 Hertz/1 Phase INTERNATIONAL Models:  
2W&G  
200 Volt/50 Hertz/  
1 Phase  
1. Prior to connecting electric service, locate transformer configuration jumper  
in junction box area.  
2W&G  
2. Remove the 208 Volt jumper and replace it with the 100 Volt jumper located  
in the literature packet from cylinder.  
(T30 Models Only)  
3. Remove small access cover from back of the fan motor. Locate the two  
internal jumper wires, brown and blue connected to motor terminals #6 and  
#2. Move brown wire from terminal #6 to terminal #2 and blue wire from  
terminal #2 to terminal #4. Be careful not to confuse light blue motor harness  
wire with the dark blue internal jumper.  
4. Carefully check motor wire connections with wiring diagram and verify that  
the motors are configured for low voltage operation before replacing covers.  
5. Repeat steps 1 through 4 for each upper and lower unit.  
6. Sign and date conversion sticker located on back of tumbler.  
7. Follow the instructions covered in Connecting Electrical Service section.  
380 Volt/50 Hertz/  
3 Phase  
400-415 Volt/50 Hertz/3 Phase Models:  
3W&G  
3W&G  
1. Prior to connecting electric service, locate transformer configuration jumper  
in junction box area.  
(T30 Models Only)  
2. Remove the 380 Volt jumper and replace it with the 415 Volt jumper located  
in the literature packet from cylinder.  
3. Repeat steps 1 and 2 for each upper and lower unit.  
4. Sign and date conversion sticker located on back of tumbler.  
5. Follow the instructions covered in Connecting Electrical Service section.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
39  
 
Electrical Requirements  
NOTE: Electrical specifications below are subject  
to change without notice. Always refer to product  
serial plate for most current specifications of  
product being installed.  
Electrical Requirements for Gas and  
Steam Models  
Refer to Table 9 and Table 10.  
NOTE: Use copper conductors only.  
NOTE: Minimum wire sizes are obtained from  
Canadian Electrical Code for 75°C Conductors and  
are intended for use as a guideline only. Electrical  
connections should be made only by a qualified  
electrical contractor in accordance with all  
applicable local and national requirements.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
For T30 Gas and Steam Models  
(For Total Machine):  
Recommended  
Fuse or  
Breaker Rating  
(Amps)  
Recommended  
Minimum  
Terminal Block  
Connections  
Required  
Serial Plate  
Voltage  
Current  
(Amps)  
Breaker  
Poles  
Conductor Size  
2
[AWG (mm )]  
L1, Neutral,  
and ground  
16.0  
20  
1
2
1
1
1
1
1
3
3
3
3
3
3
3
12 (3.31)  
14 (2.08)  
10 (5.26)  
14 (2.08)  
8 (8.37)  
120V/60 Hz/1ph  
L1, L2, Neutral,  
and ground  
8.0  
22.0  
11.6  
24.2  
15.0  
15.0  
6.4  
10  
208-240V/60Hz/  
1ph  
L1, Neutral,  
and ground  
30  
100V/60Hz/1ph  
L1, Neutral,  
and ground  
15  
200-220V/60Hz/  
1ph  
L1, Neutral,  
and ground  
35  
100V/50Hz/1ph  
200V/50Hz/1ph  
L1, Neutral,  
and ground  
20  
12 (3.31)  
12 (3.31)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
L1, Neutral,  
and ground  
20  
230-240V/50Hz/  
1ph  
L1, L2, L3,  
and ground  
10*  
10*  
10*  
10*  
10*  
10*  
10*  
200-208V/60Hz/  
3ph  
L1, L2, L3,  
and ground  
6.4  
240V/60Hz/3ph  
200V/50Hz/3ph  
L1, L2, L3,  
and ground  
5.8  
L1, L2, L3,  
and ground  
7.0  
230-240V/50Hz/  
3ph  
L1, L2, L3,  
and ground  
3.0  
380V/50 or 60Hz/  
3ph  
L1, L2, L3,  
and ground  
3.2  
400-415V/50Hz/  
3ph  
L1, L2, L3,  
and ground  
3.3  
460-480V/60Hz/  
3ph  
*
3 Phase machines should not have fuses, breakers only.  
Table 9  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
40  
 
   
Electrical Requirements  
Recommended  
For T45 Gas Models (For Total Machine):  
Terminal Block  
Recommended Fuse  
or Breaker Rating  
(Amps)  
Serial Plate  
Connections  
Voltage  
Current  
(Amps)  
Breaker  
Minimum  
Poles Conductor Size  
Required  
2
(AWG [mm ])  
L1, L2, Neutral and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
12.0  
9.6  
15  
15  
15  
2
3
3
14 (2.08)  
14 (2.08)  
14 (2.08)  
208–240V/60Hz/  
1ph  
200–208V/60Hz/  
3ph  
9.6  
240V/60Hz/3ph  
Table 10  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
41  
 
 
Electrical Requirements  
NOTE: Electrical specifications below are subject  
to change without notice. Always refer to product  
serial plate for most current specifications of  
product being installed.  
Electrical Requirements for Electric  
Models  
NOTE: Connect to individual branch circuit.  
NOTE: Minimum wire sizes are obtained from  
Canadian Electrical Code for 75°C Conductors and  
are intended for use as a guideline only. Electrical  
connections should be made only by a qualified  
electrical contractor in accordance with all  
applicable local and national requirements.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
For 21 kW T30 Electric Models:  
Recommended  
Recommended  
Terminal Block  
Connections  
Required  
Serial Plate  
Voltage  
Current  
(Amps)  
Breaker  
Poles  
Minimum  
Breaker Rating  
(Amps)  
Conductor Size  
2
[AWG (mm )]  
L1, L2, L3,  
and ground  
62**  
80  
80  
70  
70  
45  
40  
35  
3
3
3
3
3
3
3
4 (21.2)  
4 (21.2)  
4 (21.2)  
4 (21.2)  
8 (8.37)  
8 (8.37)  
8 (8.37)  
200-208V/60Hz/3ph*  
200V/50Hz/3ph*  
L1, L2, L3,  
and ground  
60**  
55**  
54**  
33**  
31**  
27**  
L1, L2, L3,  
and ground  
230-240V/50Hz/3ph*  
240V/60Hz/3ph*  
L1, L2, L3,  
and ground  
L1, L2, L3,  
and ground  
380V/50 or 60Hz/3ph*  
400-415V/50Hz/3ph*  
460-480V/60Hz/3ph*  
L1, L2, L3,  
and ground  
L1, L2, L3,  
and ground  
*
These serial plate voltages are only options available on the T30 electric models. Current (Amp) is for one pocket only.  
** Per heater on T30 electric models, each has two heaters.  
Table 11  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
42  
 
     
Steam Requirements  
NOTE: Machines require a constant 80 to 100 psig  
NOTE: To prevent water hammering, route return  
lines below outlets of steam coils.  
(5.62 to 7.03 kg/sq. cm) steam service for optimum  
operation. The maximum allowable steam pressure  
for use with 60 Hertz or 50 Hertz tumblers is  
125 psig (8.6 bar). In no case may the pressure  
exceed the above value.  
Piping Recommendations  
Trap each steam coil individually. Always keep  
the trap clean and in good working condition.  
Obtain specific steam service pipe sizes from the  
steam system supplier or a qualified steam fitter.  
When tumbler is on the end of a line of  
equipment, extend header at least 4 feet  
(1.2 meters) beyond tumbler. Install shut-off  
valve, union, check valve and bypass trap at end  
of line. If gravity return to boiler, omit trap.  
Refer to Figure 14 for proper steam pipe  
configurations.  
To prevent condensate draining from headers to  
tumbler, piping should have a minimum 12 inch  
(305 mm) rise above respective header. Do not  
make steam connection to header with a  
Insulate steam supply and return line for safety of  
operator and safety while servicing tumbler.  
Keep tumbler in good working condition. Repair  
horizontal or downward facing tee or elbow.  
or replace any worn or defective parts.  
Whenever possible, horizontal runs of steam  
lines must drain, by gravity, to respective steam  
header. Water pockets, or an improperly drained  
steam header, will provide wet steam, causing  
improper operation of tumbler. If pockets or  
improper drainage cannot be eliminated, install a  
bypass trap to drain condensate from the low  
point in the steam header to the return.  
WARNING  
All system components must have a  
125 psig (8.6 bar) working pressure.  
Shut-off valves must be installed upstream  
of the steam solenoid valve and  
downstream of each steam trap so  
components can be isolated for  
In both steam supply and steam return line, it is  
recommended that each have a pipe union and  
shut-off valve. This will enable you to disconnect  
the steam connections and service the tumbler  
while your laundry facility is in operation.  
maintenance or emergency purposes.  
All components (solenoid valve, traps)  
must be supported to minimize loads on  
the tumbler steam coil connections.  
W480R2  
Connect the steam solenoid valve to the related  
steam coil inlet connection with nipples, flex  
hoses, unions and tee.  
Strainers may require cleaning due to materials  
from hoses or pipes.  
Install vacuum breaker (optional), bucket trap  
with built-in strainer and check valve. For  
successful operation of tumbler, install trap 18  
inches (457 mm) below coil and as near to the  
tumbler as possible. Inspect trap carefully for  
inlet and outlet markings and install according to  
trap manufacturer’s instructions. If steam is  
gravity returned to boiler, omit trap but install  
optional vacuum breaker and check valve in  
return line near tumbler. Gravity return requires  
entire return plumbing be below steam coil  
outlet.  
Install union and shut-off valve in return line and  
make final pipe connections to return header.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
43  
   
Steam Requirements  
Installing Steam Trap and Making  
Condensate Return Connections  
WARNING  
The flexible steam hoses connecting the  
coil outlet connections and steam traps  
must have a minimum of 125 psig  
(pounds per square inch gauge) (8.79 kg/  
sq. cm.) working pressure. A shut-off  
valve must be installed downstream from  
each steam trap so the condensate return  
line can be isolated in event a steam trap  
requires maintenance.  
The steam trap must be installed and the coil outlet  
connections must be connected to the condensate  
return lines. The following steps outline the procedure  
for installing the steam trap and connecting the  
condensate return lines. Refer to Figure 14 for typical  
installations.  
1. Use flexible lines between steam inlet solenoid  
and steam coils, as well as outlet between steam  
coil and traps.  
Each steam trap must be supported so  
minimum load is exerted on the coil outlet  
2. If necessary, install a strainer at the end of each  
flexible hose.  
connection.  
W066  
3. Install a steam trap to each strainer.  
IMPORTANT: Steam trap must be installed a  
minimum of 18 inches (457 mm) below the steam  
coil outlet connections.  
4. Install a shut-off valve to each steam trap.  
5. Connect to the condensate return lines.  
6. For steam solenoid valve wiring connections,  
refer to Wiring Diagram supplied with tumbler.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
44  
 
Steam Requirements  
SUPPLY  
2
1
4
9
3
10  
5
6
4
8
RETURN  
7
6
5
10  
T473I  
T473I  
NOTE: Refer to Table 12 for sizing of steam lines. Piping must also be sized accordingly for length of runs,  
and number of elbows.  
1
2
3
4
5
Steam Coil  
6
7
8
9
10  
Trap with Built-In Strainer  
Vacuum Breaker (Optional)  
18 in. (457 mm) Drop  
Solenoid Valve (Supplied with machine)  
Union  
12 in. (305 mm) Riser  
Condensate Return Line from Supply Line  
Shut-Off Valve  
Check Valve  
Figure 14  
Steam Trap Size*  
Model  
T30  
Steam Pressure PSI (bar) Minimum Pipe Diameter  
15-100 (1-6.9) 3/4 in. NPT  
(Pounds Condensate/Hour)  
110  
*Based on 100 psi.  
Table 12  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
45  
 
   
Single Drop Timer  
NOTE: The following information is for  
Setting Dry Time Dipswitches  
models with an SD control suffix only.  
To change the dry time on the tumbler, combinations  
of dipswitches can be set on the control.  
Power-Up Mode  
There are eight dipswitches on the tumbler control.  
The first six switches are used to program the amount  
of additional heat time given for each coin pulse. The  
additional drying time is added to the factory default  
minimum heat time of one minute. A valve of 1 to 64  
minutes of additional drying time is available for each  
coin drop pulse.  
When power is applied to the tumbler, the IN USE  
light flashes factory status information. Following this,  
the control goes into READY Mode (light off) or RUN  
Mode if power was interrupted during a cycle (light  
on, time remaining unchanged).  
Ready Mode  
The last two switches are used to program the amount  
of additional cool down time. The additional cool  
down time is added to the factory default minimum  
cool down time of 1 minute. A value of 1 to 3  
additional minutes is available. The control is shipped  
from the factory programmed with 1 minute of  
minimum heat time, preset with 7 additional minutes  
of drying time (dipswitches 1, 2 and 3 in ON position)  
and 1 minute of minimum cool down time for a total  
time of 9 minutes for a coin pulse. For dipswitch  
settings refer to Table 13.  
In READY Mode (light off), the control waits for the  
vend to be satisfied. When vend is satisfied the control  
goes into START Mode.  
Start Mode  
In START Mode (light on), the vend has been satisfied  
but the start button has not been pressed. Time  
remaining in the cycle will not change until the start  
button is pressed. When the start button is pressed the  
machine goes into RUN Mode.  
The control reads the dipswitch settings at power-up.  
The control must be powered down to change the  
dipswitch settings.  
Run Mode  
In RUN Mode (light on), the machine is running a  
cycle and the time remaining is counting down. When  
time remaining counts down to zero, the control goes  
into READY Mode.  
To change the time for a coin pulse, the desired dry  
time dipswitches must be set to ON position. All other  
dipswitches must be in OFF position.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
46  
           
Single Drop Timer  
Dipswitch Settings  
Cool Down  
Switch Number  
Heat Switch Number  
Cool Down Per  
Cycle (in Minutes)  
Heat Time Per Coin  
1
2
3
4
5
6
7
8
Pulse (in Minutes)  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
ON  
1
1 (factory default)  
2
2
3
4
OFF  
ON  
OFF  
ON  
3
ON  
ON  
4
OFF  
ON  
OFF  
OFF  
ON  
5
ON  
6
OFF  
ON  
ON  
7
ON  
ON  
8 (factory default)  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
9
ON  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
Table 13 (Continued)  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
47  
 
   
Single Drop Timer  
Table 13 (Continued)  
Heat Switch Number  
Heat Time Per Coin  
Pulse (in Minutes)  
1
2
3
4
5
6
ON  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
OFF  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
Total Cycle Time = Heat Time + Cool Down Time  
Table 13  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
70304601  
48  
 
Adjustments  
Loading Door Switch  
Airflow Switch  
The door switch should be adjusted so the cylinder  
stops when door is opened 2 inches (51 mm) plus or  
minus 0.25 inch (6 mm). This switch is a normally  
open switch and is closed by the hinge cam when the  
door is closed. If adjustment is required, refer to  
Figure 15 and proceed as follows:  
The airflow switch is set at the factory for proper  
operation. No adjustment necessary.  
The airflow switch operation may be affected by  
shipping tape still in place, lack of make-up air, or an  
obstruction in the exhaust duct. These should be  
checked and the required corrective action taken.  
1. Close door and start tumbler, slowly open loading  
door. Cylinder and heat system should shut off  
when door is open 2 inches (51 mm) plus or  
minus 0.25 inch (6 mm).  
WARNING  
The tumbler must not be operated if the  
airflow switch does not operate properly.  
Faulty airflow switch operation may cause  
an explosive gas mixture to collect in the  
2. Slowly close the loading door. When door is  
2 inches (51 mm) from being fully closed, the  
door switch actuating bracket (located on the  
door) should depress the button and the switch  
arm with an audible “click.”  
tumbler.  
W072  
3. If the actuating bracket does not operate the  
switch at the appropriate door closure, bend the  
actuating switch bracket in or out to achieve  
proper actuation.  
IMPORTANT: Airflow switch vane must remain  
closed during operation. If it opens and closes  
during the drying cycle, this indicates insufficient  
airflow through the tumbler. If switch remains  
open, or pops open and closed during the cycle, the  
heating system will shut off. The cylinder and fan  
will continue to operate even though the airflow  
switch is indicating insufficient airflow.  
NOTE: To properly mount the airflow switch  
bracket, or in case of a load not drying, the airflow  
switch bracket may need to be checked for proper  
alignment. Be sure the locator pins are securely in  
their respective holes before tightening the bracket  
mounting screws. This will assure proper  
alignment of the airflow switch arm in the channel  
of the airflow switch bracket and prevent binding  
of the arm.  
1
TMB2077N  
1
Airflow Switch Actuating Bracket  
Figure 15  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
49  
       
Adjustments  
Door Strike  
The door strike must be adjusted to have sufficient  
tension to hold loading door closed against force of the  
load tumbling against it. There is proper adjustment of  
pull force when 8 to 15 pounds (35.6 N – 66.7 N) is  
required to open door.  
If adjustment is required, refer to Figure 16 and  
proceed as follows:  
To adjust, open door, loosen acorn nut, and turn door  
strike screw in or out as required. Retighten acorn nut.  
1
2
9  
TMB1990N  
1
2
Door Strike Screw  
Acorn Nut  
Figure 16  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
50  
   
Removing Tumbler from Service  
If the tumbler is to be removed from service, perform  
the following steps where applicable:  
Turn off electrical supply external to machine.  
Turn off electrical disconnect on machine.  
Turn off gas supply external to machine.  
Turn off manual gas shut-off valve on machine.  
Turn off steam supply external to machine.  
Remove all electric, gas and steam connections  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
70304601  
51  
 

3Com Security Camera FlexWATCH 3110 User Manual
AB Soft Power Supply ATX 12V User Manual
ACCO Brands Range GBC 2064WF 1 User Manual
Accton Technology Switch ES5508 User Manual
Acer Personal Computer M5810 User Manual
Agri Fab Lawn Mower 45 0265 User Manual
Allied Telesis Switch XEM 12S User Manual
American Audio Turntable POWERDRIVE22pdf User Manual
American Standard Hot Tub 047186 0070A User Manual
ATN Inc Binoculars PVS7 User Manual