Alliance Laundry Systems Clothes Dryer TMB795C User Manual

Drying Tumblers  
50 Pound Capacity  
75 Pound Capacity  
Through Serial No. 0903xxxxx  
NOTA: Para bajar una  
copia de estas  
instrucciones en  
español, visite  
TMB795C  
TMB795C  
Keep These Instructions for Future Reference.  
(If this machine changes ownership, this manual must accompany machine.)  
Part No. M414905R12  
March 2009  
 
Installation must conform with local codes or, in the absence of local codes, with:  
In the U.S.A., installation must conform to the latest edition of the American National Standard Z223.1/  
NFPA 54 “National Fuel Gas Code” and Standard ANSI/NFPA 70 “National Electric Code.”  
In Canada, installation must comply with Standards CAN/CSA-B149.1 or Natural Gas and Propane  
Installation Code and CSA C22.1, latest edition, Canadian Electric Code, Part I.  
In Australia, installation must comply with the Australian Gas Association Installation Code for Gas  
Burning Appliances and Equipment.  
WARNING  
FOR YOUR SAFETY, the information in this manual must be followed to minimize the risk  
of fire or explosion or to prevent property damage, personal injury or death.  
W033  
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or  
any other appliance.  
• WHAT TO DO IF YOU SMELL GAS:  
– Do not try to light any appliance.  
– Do not touch any electrical switch; do not use any phone in your building.  
– Clear the room, building or area of all occupants.  
– Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s  
instructions.  
– If you cannot reach your gas supplier, call the fire department.  
• Installation and service must be performed by a qualified installer, service agency or the gas  
supplier.  
W052  
MISE EN GARDE  
POUR VOTRE SÉCURITÉ, les informations de ce guide doivent être respectées afin de  
réduire les risques d’incendie, d’explosion ou d’éviter les dommages matériels,  
personnels ou blessures mortelles.  
W033R3QU  
• Ne pas entreposer ou utiliser d’essence ou toutes autres vapeurs et liquides inflammables à  
proximité de cette machine ou de tout autre appareil.  
• QUE FAIRE EN CAS D’ODEUR DE GAZ :  
– Ne pas mettre d’appareil en marche.  
– Ne pas toucher aux interrupteurs électriques ; ne pas utiliser le téléphone des lieux.  
– Évacuer la pièce, le bâtiment ou la zone de tous les occupants.  
– Appeler immédiatement le fournisseur de gaz de la maison d’un voisin. Respecter les  
instructions communiquées par le fournisseur.  
– Si vous ne pouvez pas joindre le fournisseur de gaz, appeler le service d’incendie.  
• L’installation et l’entretien doivent être effectués par un installateur, service d’entretien  
qualifiés ou par le fournisseur de gaz.  
W052R5QU  
IMPORTANT: Information must be obtained from a local gas supplier on instructions to be followed if the  
user smells gas. These instructions must be posted in a prominent location. Step-by-step instructions of the  
above safety information must be posted in a prominent location near the tumbler for customer use.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
1
 
WARNING  
• Installation of unit must be performed by a qualified installer.  
• Install tumbler according to manufacturer’s instructions and local codes.  
• DO NOT install a tumbler with flexible plastic venting materials. If flexible metal (foil type)  
duct is installed, it must be of a specific type identified by the appliance manufacturer as  
suitable for use with tumbler. Refer to section on connecting exhaust system. Flexible  
venting materials are known to collapse, be easily crushed, and trap lint. These conditions  
will obstruct tumbler airflow and increase the risk of fire.  
W752  
FOR YOUR SAFETY  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or  
any other appliance.  
W053  
MISE EN GARDE  
• L'unité doit être installée par un installateur qualifié.  
• Installer la sécheuse conformément aux instructions du fabricant et aux codes locaux.  
• NE PAS installer une sécheuse avec des matériaux d'aération souples en plastique. Si un  
conduit d'aération souple en métal (de type feuille mince) est utilisé, il doit être d'un type  
spécifiquement mentionné par le fabricant de l'appareil comme convenable pour utilisation  
avec sécheuses. Se reporter à la section sur la façon de connecter le système d'évacuation.  
Les matériaux d'aération souples risquent de s'affaisser, ils s'écrasent facilement, et les  
fibres et les peluches s'y accumulent. Ces conditions obstruent l'écoulement de l'air et  
augmentent les risques d'incendie.  
W752QU  
POUR VOTRE SÉCURITÉ  
Ne pas entreposer ou utiliser d’essence ou toutes autres vapeurs et liquides inflammables à  
proximité de cette unité ou de tout autre appareil.  
W053R2QU  
The following information applies to the state of Massachusetts, USA.  
• This appliance can only be installed by a Massachusetts licensed plumber or gas fitter.  
• This appliance must be installed with a 36 inch (91 cm) long flexible gas connector.  
• A "T-Handle" type gas shut-off valve must be installed in the gas supply line to this appliance.  
• This appliance must not be installed in a bedroom or bathroom.  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
M414905  
2
 
Introduction.........................................................................................  
5
Table of  
Contents  
Safety Information..............................................................................  
8
Specifications and Dimensions........................................................... 11  
Installation........................................................................................... 17  
Exhaust Requirements ....................................................................... 30  
Gas Requirements............................................................................... 35  
Electrical Requirements..................................................................... 40  
© Copyright 2009, Alliance Laundry Systems LLC  
All rights reserved. No part of the contents of this book may be reproduced or transmitted in any form or by any  
means without the expressed written consent of the publisher.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
3
 
Steam Requirements........................................................................... 48  
Installing Steam Trap and Making Condensate  
Return Connections............................................................................ 49  
Single Drop Timer .............................................................................. 51  
Rotary Coin Drop Timer.................................................................... 54  
Adjustments......................................................................................... 55  
Removing Tumbler from Service...................................................... 61  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
M414905  
4
 
Introduction  
Model Identification  
Information in this manual is applicable to these models:  
Gas  
Steam/Thermal Oil  
Electric  
AT050E  
CHD50E2-CT050E  
CHD50E2-CU050E  
DR55E2-BT050E  
DR55E2-BU050E  
GT050E  
GU050E  
HT050E  
HU050E  
IPD50E2-IT050E  
ST050E  
AT050L  
AT050N  
HT050N  
HU050L  
AT050S  
UT050T  
CHD50S2-CT050S UU050S  
CHD50S2-CU050S UU050T  
CHD50G2-CA050L HU050N  
CHD50G2-CA050N IPD50G2-IT050L  
CHD50G2-CT050L IPD50G2-IT050N  
CHD50G2-CT050N NT050L  
CHD50G2-CU050L NT050N  
CHD50G2-CU050N SA050L  
CT050T  
CU050T  
YT050S  
YT050T  
DR55S2-BT050S  
DR55S2-BT050T  
DR55S2-BU050S  
DR55S2-BU050T  
GT050S  
DR55G2-BA050L  
SA050N  
DR55G2-BA050N ST050D  
DR55G2-BT050D  
DR55G2-BT050L  
DR55G2-BT050N  
DR55G2-BU050L  
ST050L  
ST050N  
SU050L  
SU050N  
GU050S  
HT050S  
HT050T  
HU050S  
50  
Pound  
SU050E  
UT050E  
UU050E  
DR55G2-BU050N UA050L  
HU050T  
YT050E  
GT050L  
GT050N  
GU050L  
GU050N  
HA050L  
HA050N  
HT050D  
HT050L  
UA050N  
UT050L  
UT050N  
UU050L  
UU050N  
YT050L  
YT050N  
IPD50S2-IT050S  
IPD50S2-IT050T  
ST050S  
ST050T  
SU050S  
SU050T  
UT050S  
AT075L  
AT075N  
HU075N  
IPD75G2-IT075L  
AT075S  
CHD75S2-CT075S YT075S  
CHD75S2-CU075S YT075T  
CT075T  
CU075T  
DR80S2-BT075S  
DR80S2-BT075T  
DR80S2-BU075T  
DR80S2-BU075S  
GT075S  
UU075T  
AT075E  
CHD75E2-CT075E  
CHD75E2-CU075E  
DR80E2-BT075E  
DR80E2-BU075E  
GT075E  
GU075E  
HT075E  
HU075E  
IPD75E2-IT075E  
ST075E  
CHD75G2-CA075L IPD75G2-IT075N  
CHD75G2-CA075N NT075L  
CHD75G2-CT075L NT075N  
CHD75G2-CT075N SA075L  
CHD75G2-CU075L SA075N  
CHD75G2-CU075N ST075D  
DR80G2-BA075L  
DR80G2-BA075N ST075N  
DR80G2-BT075D  
DR80G2-BT075L  
DR80G2-BT075N  
DR80G2-BU075L  
YU075S  
YU075T  
ST075L  
STF75L  
STF75N  
SU075L  
SU075N  
GU075S  
HT075S  
HT075T  
HU075S  
SU075E  
UB075E  
UT075E  
75  
Pound  
DR80G2-BU075N UA075L  
HU075T  
UU075E  
GT075L  
GT075N  
GU075L  
GU075N  
HA075L  
HA075N  
HT075D  
HT075L  
HT075N  
HU075L  
UA075N  
UT075L  
UT075N  
UTF75L  
UTF75N  
UU075L  
UU075N  
YT075L  
YT075N  
IPD75S2-IT075S  
IPD75S2-IT075T  
ST075S  
ST075T  
SU075S  
SU075T  
UT075S  
UT075T  
UU075S  
YT075E  
YU075E  
Control suffixes listed on the following page.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
5
 
     
Introduction  
Includes models with the following control suffixes:  
3O –DX4 OPL  
DO –DMP OPL  
RD –reversing DMP OPL  
3V –DX4 vended  
DV –DMP vended  
RM –reversing OPL micro  
3X –DX4 prep for coin  
BC –basic electronic, coin  
BL –basic electronic, central pay  
BU –basic electronic, prep card-open  
BX –basic electronic, prep for coin  
BY –basic electronic, prep for card  
CD –rotary coin drop  
DX –DMP prep for coin  
MT –manual timer  
RQ –reversing dual digital timer  
RT –reversing manual timer  
SD –single drop  
NC –NetMaster coin  
NR –NetMaster card  
NX –NetMaster, prep for coin  
NY –NetMaster, prep for card  
OM –OPL micro  
SX –single drop, prep for coin  
ZC –NetMaster network, coin  
ZR –NetMaster network, card  
ZX –NetMaster network, prep for coin  
ZY –NetMaster network, prep for card  
CX –prep for coin  
QT –dual digital timer  
R3 –reversing DX4 OPL  
CY –prep for card  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
6
 
Introduction  
Customer Service  
Wiring Diagram  
If literature or replacement parts are required, contact  
the source from which the machine was purchased or  
contact Alliance Laundry Systems at (920) 748-3950  
for the name and address of the nearest authorized  
parts distributor.  
The wiring diagram is located in the junction or  
contactor box.  
Models starting Serial No. 0309_____ or later will  
have the wiring diagram part number in the lower  
portion of the electrical data on the serial plate.  
For technical assistance, call (920) 748-3121.  
Serial Plate Location  
When calling or writing for information about your  
product, be sure to mention model and serial numbers.  
Model and serial numbers are found on serial plate on  
the rear of machine and inside door.  
0
L
W
O
O
N
C
5
O
D
5
1
E
R
U
0
AT  
OW  
1
R
L
E
P
0
0
1
M
E
T
T
A
E
H
H
IG  
0
6
0
2
H
1
0
5
0
3
0
4
H
S
O
U
P
T
T
R
A
T
S
1
TMB803N  
1
Serial Plate  
Conversion Table  
To Obtain  
kCal  
Multiply  
By  
Multiply  
Pounds/sq. inch  
Pounds/sq. inch  
Pounds (lbs.)  
Boiler Horsepower  
Boiler Horsepower  
CFM  
By  
To Obtain  
Bars  
Btu  
Btu  
Inch  
0.252  
1055  
25.4  
0.06895  
0.070  
0.454  
33,479  
34.5  
Joules  
kg/sq. cm  
Kilograms  
Btu/hr.  
Millimeters  
Pounds/sq. inch  
kPa  
Inches W.C.  
Inches W.C.  
0.036  
0.249  
6.895  
28.32  
lbs. steam/hr.  
liters/second  
Btu/hr.  
2
lb/inch (psi)  
kPa  
0.471  
3414  
3
ft  
Liters  
kW  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
7
 
     
Safety Information  
Precautionary statements (“DANGER,” “WARNING,”  
NOTE: The word “NOTE” is used to communicate  
installation, operation, maintenance or servicing  
information that is important but not hazard  
related.  
and “CAUTION”), followed by specific instructions,  
are found in this manual and on machine decals. These  
precautions are intended for the personal safety of the  
operator, user, servicer, and those maintaining the  
machine.  
WARNING  
DANGER  
Failure to install, maintain, and/or operate  
this machine according to manufacturer’s  
instructions may result in conditions which  
can produce serious injury, death and/or  
Indicates an imminently hazardous  
situation that, if not avoided, will cause  
severe personal injury or death.  
property damage.  
W051R1  
WARNING  
NOTE: The WARNING and IMPORTANT  
instructions appearing in this manual are not  
meant to cover all possible conditions and  
situations that may occur. It must be understood  
that common sense, caution and carefulness are  
factors which CANNOT be built into this tumbler.  
These factors MUST BE supplied by the person(s)  
installing, maintaining or operating the tumbler.  
Indicates a hazardous situation that, if not  
avoided, could cause severe personal  
injury or death.  
CAUTION  
Indicates a hazardous situation that, if not  
avoided, may cause minor or moderate  
personal injury or property damage.  
Always contact your dealer, distributor, service agent  
or the manufacturer on any problems or conditions you  
do not understand.  
Additional precautionary statements (“IMPORTANT”  
and “NOTE”) are followed by specific instructions.  
IMPORTANT: The word “IMPORTANT” is used  
to inform the reader of specific procedures where  
minor machine damage will occur if the procedure  
is not followed.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
8
 
Safety Information  
Save These Instructions  
14. The interior of the tumbler and the exhaust duct  
should be cleaned periodically by qualified  
service personnel.  
Important Safety Instructions  
WARNING  
15. If not installed, operated and maintained in  
accordance with the manufacturer’s instructions  
or if there is damage to or mishandling of this  
product’s components, use of this product could  
expose you to substances in the fuel or from fuel  
combustion which can cause death or serious  
illness and which are known to the State of  
California to cause cancer, birth defects or other  
reproductive harm.  
Hazardous Voltage. Can cause shock, burn  
or cause death. Allow machine power to  
remain off for two minutes prior to working  
in and around AC inverter drive.  
W359  
1. Read all instructions before using the tumbler.  
2. Refer to the GROUNDING INSTRUCTIONS  
for the proper grounding of the tumbler.  
16. Tumbler will not operate with the loading door  
open. DO NOT bypass the door safety switch to  
permit the tumbler to operate with the door open.  
The tumbler will stop tumbling when the door is  
opened. Do not use the tumbler if it does not stop  
tumbling when the door is opened or starts  
tumbling without pressing or turning the START  
mechanism. Remove the tumbler from use and  
call for service.  
3. Do not dry articles that have been previously  
cleaned in, washed in, soaked in, or spotted with  
gasoline, dry cleaning solvents, other flammable  
or explosive substances as they give off vapors  
that could ignite or explode.  
4. Do not allow children on or in the tumbler. This  
appliance is not intended for use by young  
children or infirm persons without supervision.  
Young children should be supervised to ensure  
that they do not play with the appliance.  
17. Tumbler will not operate with lint panel open.  
DO NOT bypass lint panel safety switch to  
permit the tumbler to operate with the lint panel  
open.  
5. Before the tumbler is removed from service or  
discarded, remove the door to the drying  
compartment and the door to the lint  
compartment.  
18. Do not put articles soiled with vegetable or cooking  
oil in the tumbler, as these oils may not be  
removed during washing. Due to the remaining  
oil, the fabric may catch on fire by itself.  
6. Do not reach into the tumbler if the cylinder is  
revolving.  
19. To reduce the risk of fire, DO NOT put clothes  
which have traces of any flammable substances  
such as machine oil, flammable chemicals,  
thinner, etc. or anything containing wax or  
chemicals such as in mops and cleaning cloths, or  
anything dry-cleaned at home with dry-cleaning  
solvent in the tumbler.  
7. Do not install or store the tumbler where it will  
be exposed to water and/or weather.  
8. Do not tamper with the controls.  
9. Do not repair or replace any part of the tumbler,  
or attempt any servicing unless specifically  
recommended in the user-maintenance  
instructions or in published user-repair  
instructions that you understand and have the  
skills to carry out.  
20. Use the tumbler only for its intended purpose,  
drying fabrics.  
21. ALWAYS disconnect and lockout the electrical  
power to the tumbler before servicing. Disconnect  
power by shutting off appropriate breaker or fuse.  
10. Do not use fabric softeners or products to  
eliminate static unless recommended by the  
manufacturer of the fabric softener or product.  
22. Install this tumbler according to the  
INSTALLATION INSTRUCTIONS. All  
connections for electrical power, grounding, and  
gas supply must comply with local codes and be  
made by licensed personnel when required.  
11. To reduce the risk of fire, DO NOT DRY plastics  
or articles containing foam rubber or similarly  
textured rubberlike materials.  
12. Always clean the lint filter daily.  
13. Keep area around the exhaust opening and  
adjacent surrounding area free from the  
accumulation of lint, dust and dirt.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
9
 
Safety Information  
23. Remove laundry immediately after tumbler  
stops.  
29. DO NOT bypass any safety devices.  
30. Solvent vapors from dry-cleaning machines  
create acids when drawn through the heater of the  
drying unit. These acids are corrosive to the  
tumbler as well as to the laundry load being  
dried. Be sure make-up air is free of solvent  
vapors.  
24. Always read and follow manufacturer’s  
instructions on packages of laundry and cleaning  
aids. Heed all warnings or precautions. To reduce  
the risk of poisoning or chemical burns, keep  
them out of reach of children at all times  
(preferably in a locked cabinet).  
31. Failure to install, maintain, and/or operate this  
machine according to the manufacturer’s  
25. Do not tumble fiberglass curtains and draperies  
unless the label says it can be done. If they are  
dried, wipe out the cylinder with a damp cloth to  
remove particles of fiberglass.  
instructions may result in conditions which can  
produce bodily injury and/or property damage.  
26. Always follow the fabric care instructions  
supplied by the garment manufacturer.  
WARNING  
To reduce the risk of serious injury, install  
lockable door(s) to prevent public access  
27. Never operate the tumbler with any guards and/or  
panels removed.  
to rear of tumblers.  
W055  
28. DO NOT operate the tumbler if it is smoking,  
grinding, has missing or broken parts.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
10  
Specifications and Dimensions  
Specifications  
50 Pound  
75 Pound  
F75  
63 dBA  
69 dBA  
67 dBA  
Noise level measured during  
operation at operator position of  
3.3 feet (1 meter) in front of  
machine and 5.2 feet (1.6 meters)  
from floor.  
545  
(247)  
615  
(279)  
710  
(322)  
Net Weight (approximate):  
Pounds (kg)  
37 x 30  
(940 x 762)  
37 x 36  
(940 x 914)  
37 x 36  
(940 x 914)  
Cylinder Size:  
Inches (mm)  
50  
(22.7)  
75  
(34)  
75  
(34)  
Cylinder Capacity (dry weight):  
Pounds (kg)  
8
8
10  
(254)  
Air Outlet Diameter:  
Inches (mm)  
(203)  
(203)  
0.5  
(1.3)  
0.5  
(1.3)  
0.5  
(1.3)  
Maximum Static Back Pressure:  
W.C.I. (mbar)  
750  
(354)  
Gas/Steam 60 Hz 920 (434)  
Gas/Steam 50 Hz 750 (354)  
1100  
(518)  
Maximum Airflow:  
C.F.M. (L/sec.)  
Electric  
750 (354)  
Motor Horsepower:  
Nonreversing  
Reversing  
Fan  
1/2  
3/4  
N/A  
1/3  
1/3  
1/3  
1/3  
1
1/3  
Cylinder  
Gas Models  
1/2 in. NPT  
1/2 in. NPT  
3/4 in. NPT  
Gas Connection  
120,000  
(126.6)  
165,000  
(174.1)  
215,000  
(227)  
Gas Burner Rating:  
Btu/hr (Mj/hr)  
Electric Models  
21 kW (240 V/50 Hz)  
30 kW (other voltages)  
30 kW  
N/A  
Heating Element Rating:  
Kilowatts (kW)  
Steam Models  
3/4 in. NPT  
3/4 in. NPT  
N/A  
N/A  
Steam Connection  
5.1  
(177,500)  
6.1  
(210,300)  
Steam Coil Rating:  
Boiler Horsepower (Btu/hr)  
N/A = Not Applicable  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
11  
 
 
Specifications and Dimensions  
Cabinet Dimensions  
C
E
B
D
A
F
G
TMB2210N  
A
B
Models  
C
D
E
F
G
*
**  
*
**  
50  
30.75 in. 28.75 in. 28.25 in. 33.87 in.  
(781 mm) (730 mm) (717 mm) (860 mm) (1194 mm) (1946 mm) (981 mm) (838 mm) (749 mm)  
47 in.  
76.625 in. 38.625 in.  
33 in.  
29.5 in.  
Pound  
Gas and  
Electric  
50  
Pound  
Steam  
30.75 in. 28.75 in. 28.25 in. 33.87 in.  
(781 mm) (730 mm) (717 mm) (860 mm) (1194 mm) (2032 mm) (981 mm) (838 mm) (749 mm)  
47 in.  
80 in.  
38.625 in.  
33 in.  
29.5 in.  
75  
30.75 in. 28.75 in. 28.25 in. 33.87 in.  
(781 mm) (730 mm) (717 mm) (860 mm) (1346 mm) (1946 mm) (981 mm) (838 mm) (902 mm)  
53 in.  
76.625 in. 38.625 in.  
33 in.  
35.5 in.  
Pound  
Gas and  
Electric  
75  
Pound  
Steam  
30.75 in. 28.75 in. 28.25 in. 33.87 in.  
(781 mm) (730 mm) (717 mm) (860 mm) (1346 mm) (2032 mm) (981 mm) (838 mm) (902 mm)  
53 in.  
80 in.  
38.625 in.  
33 in.  
35.5 in.  
30.75 in. 28.75 in. 28.25 in. 33.87 in.  
(781 mm) (730 mm) (717 mm) (860 mm) (1346 mm) (1946 mm) (981 mm) (838 mm) (902 mm)  
53 in.  
76.625 in. 38.625 in.  
33 in.  
35.5 in.  
F75  
Gas  
* A, H, S and U models prior to Serial No. 0308001307 and all other models.  
** A, H, N, S and U models after Serial No. 0308001307.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
12  
 
Specifications and Dimensions  
Exhaust Outlet Locations  
B
C
A
TMB811N  
Models  
A
B
C
5.375 in.  
(137 mm)  
8 in.  
(203 mm)  
13.375 in.  
(340 mm)  
50/75 Pound  
6.5 in.  
(165 mm)  
10 in.  
(254 mm)  
6.5 in.  
(165 mm)  
F75  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
13  
 
 
Specifications and Dimensions  
Gas Connection Locations  
A
B
TMB812N  
TMB812N  
Models  
Diameter  
A
B
1/2 in. NPT  
15.5 in.  
(394 mm)  
65.75 in.  
(1670 mm)  
50 Pound  
1/2 in. NPT  
3/4 in. NPT  
15.75 in.  
(400 mm)  
65.75 in.  
(1670 mm)  
75 Pound  
F75  
15.75 in.  
(400 mm)  
65.75 in.  
(1670 mm)  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
14  
 
 
Specifications and Dimensions  
Electrical Connection Locations  
A
A
B
B
T
GAS AND STEAM  
ELECTRIC  
TMB813N  
Models  
A
B
9.5 in.  
(241 mm)  
63.5 in.  
(1613 mm)  
Gas and Steam  
19 in.  
(483 mm)  
64 in.  
(1626 mm)  
Electric  
NOTE: These figures are approximate dimensions only.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
15  
 
 
Specifications and Dimensions  
Steam Connection Locations  
A
C
B
D
TMB814N  
TMB814N  
Models  
Diameter  
A
B
C
D
3/4 in. NPT  
15.25 in.  
(387 mm)  
72.75 in.  
(1848 mm)  
7.5 in.  
(190 mm)  
64.75 in.  
(1645 mm)  
50/75 Pound  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
16  
 
 
Installation  
Pre-Installation Inspection  
Materials Required (Obtain Locally)  
Upon delivery, visually inspect the crate, carton and  
parts for any visible shipping damage. If the crate,  
carton, or cover is damaged or signs of possible  
damage are evident, have the carrier note the condition  
on the shipping papers before the shipping receipt is  
signed, or advise the carrier of the condition as soon as  
it is discovered.  
One Single Pole fused disconnect  
switch or circuit breaker on 1 Phase  
models.  
All Models  
Circuit breaker on 3 Phase models.  
One gas shut-off valve for gas service  
line to each tumbler.  
Gas Models  
One steam shut-off valve for steam  
service line to be connected upstream of  
solenoid steam valve.  
Two steam shut-off valves for each  
condensate return line.  
Flexible steam hoses with a 125 psig  
(pounds per square inch gauge)  
(8.79 kg/sq. cm) working pressure for  
connecting steam coils. Refer to Figure  
23 for sizing and connection  
Remove the crate and protective cover as soon as  
possible and check the items listed on the packing list.  
Advise the carrier of any damaged or missing articles  
as soon as possible. A written claim should be filed  
with the carrier immediately if articles are damaged or  
missing.  
Steam Models  
IMPORTANT: Remove the shipping tape from the  
two back draft dampers located in the exhaust  
outlet.  
configurations.  
IMPORTANT: Warranty is void unless tumbler is  
installed according to instructions in this manual.  
Installation should comply with minimum  
specifications and requirements detailed in this  
manual and applicable local gas fitting regulations,  
municipal building codes, water supply regulations,  
electrical wiring regulations, and any other  
relevant statutory regulations. Due to varied  
requirements, applicable local codes should be  
thoroughly understood and all pre-installation  
work arranged for accordingly.  
Two steam traps for steam coil outlets  
to condensate return line.  
Optional – Two vacuum breakers for  
condensate return lines.  
IMPORTANT: Keep tumbler area clear and free  
from combustible materials, gasoline and other  
flammable vapors and liquids.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
17  
   
Installation  
A typical tumbler enclosure is shown in Figure 1. Note  
the minimum and maximum dimensions. Local codes  
and ordinances must be complied with.  
Location Requirements  
The tumbler must be installed on a level floor. Floor  
covering materials such as carpeting or tile should be  
removed.  
WARNING  
To reduce the risk of serious injury, install  
lockable door(s) to prevent public access  
To assure compliance, consult local building code  
requirements. The tumbler must not be installed or  
stored in area where it will be exposed to water and/or  
weather.  
to rear of tumblers.  
W055  
IMPORTANT: DO NOT block the airflow at the  
rear of the tumbler with laundry or other articles.  
Doing so would prevent adequate air supply to the  
combustion chamber of the tumbler.  
IMPORTANT: Install tumblers with sufficient  
clearance for servicing and operation, refer to  
Figure 1.  
WARNING  
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible  
construction must conform to the minimum clearances.  
W056  
4
1
3
2
5
6
7
8
TMB2131N  
NOTE: Shaded areas indicate adjacent structure.  
1
2
0.5 in. (13 mm) recommended between machines for removal or installation  
Allow 2-4 in. (51-102 mm) opening at top of machine to aid in removal or installation. A removable trim piece  
may be used to conceal the opening; zero clearance allowed for trim.  
3
4
5
6
7
8
4 in. (102 mm) maximum header thickness  
12 in. (305 mm) minimum clearance permitted for remainder  
Guard  
Provision for make-up air  
24 in. (610 mm) minimum, 36 in. (914 mm) recommended for maintenance purposes  
0.25 in. (6 mm) recommended for removal or installation purposes, zero clearance allowed  
Figure 1  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
18  
 
   
Installation  
Position and Level the Tumbler  
Bolt-On Angle Option  
Remove lint panel door, and unscrew the four shipping  
bolts (one at each corner). Remove tumbler from skid.  
50 Pound Tumblers Only  
This option allows the tumbler depth to be reduced to  
34 5/16 inches. The tumbler should then fit through a  
36 inch door opening (actual 34 1/2 inches).  
NOTE: Do not throw bolts away – they are the  
leveling legs.  
NOTE: Refer to appropriate troubleshooting  
manual for details on the following procedures.  
Remove four nuts from the literature package, and  
screw one fully on to each leveling leg.  
Screw the four leveling legs (bolts) back into the level  
adjusting fittings from the bottom.  
1. Remove the loading door, access panel, front  
panel and lint panel. Refer to Figure 3.  
Slide tumbler to its permanent location. Adjust the  
leveling legs until the unit is level, or no more than  
0.125 inch (3.2 mm) higher in the front. Refer to  
Figure 2. Tumbler must not rock. Lock leveling legs  
with nuts previously installed.  
3
4
2
NOTE: The front of the tumbler should be slightly  
higher than the rear (approximately 0.125 inch,  
3.18 mm). This will prevent the clothes, while  
tumbling, from wearing on the door glass gasket.  
1
IMPORTANT: Keep tumbler as close to floor as  
possible. The unit must rest firmly on floor so  
weight of tumbler is evenly distributed.  
5
TMB2014K  
1
2
3
4
5
Loading Door  
Front Panel  
Access Panel  
Cylinder  
Lint Panel  
T483I  
Figure 3  
Figure 2  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
19  
 
       
Installation  
3
4
X
3
5
4
5
2
6
X
2
2
7
1
1
6
1
7
8
TMB2015K  
TMB2016K  
1
Number of Shims for this Channel  
Cylinder Head  
1
2
3
4
5
6
7
8
Trunnion Housing  
Junction/Contactor Box  
Vertical Trunnion Channel  
Cylinder Pulley  
Drive Guard  
2
3
4
5
6
7
Trunnion  
Channel Identifier  
Shims  
Channel Location  
Number of Shims for this Channel  
Exhaust Thimble  
Motor  
Motor Bracket  
Figure 5  
Figure 4  
10. Remove the motor(s) and motor bracket(s). Refer  
to Figure 4.  
2. Remove the drive guard. Refer to Figure 4.  
3. Remove the drive belts. Refer to Figure 4.  
4. Remove the cylinder pulley and shaft key.  
11. Unbolt and remove the two vertical trunnion  
channels.  
12. Remove the junction/contactor box. Refer to  
5. Pull the cylinder out through the front of the  
tumbler. Refer to Figure 3.  
13. Remove the exhaust thimble.  
6. To ensure proper cylinder balance for  
reassembly, mark each channel’s original  
location on cylinder head and number of shims  
for each channel before removal. Refer to Figure  
5.  
14. The gas supply line may require removal if it  
extends past the rear panel. If so, disconnect the  
union located between the gas and shutoff valves  
and remove the assembly out through the front of  
the tumbler.  
7. Remove the complete idler assembly.  
8. Remove the trunnion housing. Refer to Figure 4.  
9. Disconnect the motor harness(s).  
15. Remove the tumbler from the crate base and slide  
it through the door, sideways.  
16. Refer to the appropriate troubleshooting manual,  
installation manual and wiring diagram to  
reassemble and install the tumbler correctly.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
20  
   
Installation  
To Reverse the Loading Door  
1
A, H, S and U models after serial number  
0308001307  
8
The tumbler is delivered with a right hinged door, but  
the door can be changed to a left hinged position.  
7
WARNING  
2
5
4
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
3
• Close gas shut-off valve to gas tumbler  
before servicing.  
4
• Close steam valve to steam tumbler  
before servicing.  
• Never start the tumbler with any guards/  
panels removed.  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
tumbler is properly grounded.  
5
W002  
6
1. Disconnect power supply to tumbler.  
TMB1994N  
2. Unlock and remove control panel. Remove two  
control assembly mounting screws from right  
side. Swing open control to access upper flange  
right guide lug assembly. Refer to Figure 6.  
1
2
3
4
5
6
7
8
Control Assembly Mounting Screw  
Control Assembly  
Guide Lug Assembly  
Side Screw  
3. Remove lint panel.  
Screw  
IMPORTANT: Support door and hinge assembly  
securely to prevent it from dropping once side  
screws are removed from door hinge lug.  
Lint Panel  
Front Panel  
Control Panel  
Figure 6  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
21  
 
   
Installation  
4. Remove four front panel screws. Refer to  
Figure 6. Keep door hinge cams in place on door  
hinge lug. Pull lug and door assembly off as one  
piece. Refer to Figure 7.  
7. Cut wire ties along right side of machine to  
remove door switch harness from lint panel  
switch harness bundle. Be careful not to damage  
harness wires. Refer to Figure 8.  
5. Remove remaining front panel screws. four on  
the top and four on the bottom. Refer to Figure 6.  
Disconnect door switch harness from switch.  
Take off front panel. Refer to Figure 7.  
8. Reroute door switch harness up through top  
panel, along underside of front flange, through  
screw cable clamp, back down through top panel  
and into upper left quadrant of cylinder  
enclosure. Refer to Figure 8.  
6. Exchange switch and plug locations. Depress  
tabs with an adjustable pliers to remove plug and  
switch from front panel. Reinstall switch,  
orienting button toward center of machine.  
Reinstall plug in switch’s previous location.  
Refer to Figure 7.  
1
7
1
2
6
5
3
4
3
2
TMB1996N  
1
2
3
4
5
6
7
Screw Cable Clamp  
4
Beginning Location of Door Switch Harness  
Original Switch Location  
Lint Panel Switch Harness  
Wire Ties  
5
TMB1995N  
1
2
3
4
5
Plug  
Switch  
Original Plug Location  
Top Panel  
Side Screw  
Door Hinge Lug  
Door Assembly  
Figure 8  
Figure 7  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
22  
 
   
Installation  
9. Place front panel on machine, loosely attach four  
bottom screws. Connect door switch harness to  
switch in new location. Install door assembly and  
four front panel side screws loosely. Refer to  
1
4
10. Check lint panel fit, adjusting front panel up or  
down as required. Tighten four front panel side  
screws to maintain position of front panel for  
proper lint panel clearance.  
11. Remove lint panel. Fully tighten bottom screws  
on front panel.  
12. Reinstall top screws and guide lugs.  
13. Adjust door catch if necessary to allow  
7 – 15 pounds pull (0.48 – 1.03 bar) at center of  
handle.  
14. Reinstall control assembly using mounting  
screws.  
3
2
15. Reinstall control panel and lint panel.  
TMB1997N  
IMPORTANT: Restore power to tumbler and test  
for proper operation of loading door switch.  
Tumbler should not start with door open; an  
operating tumbler should stop when door is  
opened.  
1
Switch (New location)  
Plug (New location)  
Door Assembly  
2
3
4
Side Screw  
NOTE: If machine is converted back to right hand  
hinge operation, the door switch harness must be  
rerouted and rebundled with the lint panel switch  
harness. Wire ties must be used to secure harnesses.  
Wire ties (Part No. 55881) can be ordered from  
RSPC.  
Figure 9  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
23  
 
 
Installation  
8. Load the cylinder with a full load of clean rags  
and run to remove oil or dirt from cylinder.  
Before Placing Tumbler into Service  
1. Remove or open all panels and check accessible  
bolts, nuts, screws, terminals and fittings for  
tightness.  
9. Check the airflow switch operation refer to  
Adjustments section. The heating systems should  
shut off when the lint panel is opened a  
maximum of 1.5 inches (38 mm).  
2. Check belt tension and adjust if necessary. Refer  
to Adjustments section.  
The airflow switch operation may be affected by  
shipping tape still in place, lack of make-up air,  
or an obstruction in the exhaust duct. These  
should be checked and the required corrective  
action taken before attempting to adjust the  
airflow switch. To adjust the airflow switch, refer  
to Adjustments section.  
3. Replace all panels and guards.  
4. Turn on electrical supply to tumbler.  
5. Open the supply valve for gas or steam heated  
tumblers.  
6. After performing the previous checks, start the  
tumbler by pressing START. (Refer to the  
Operating Manual for detailed instructions.)  
Release the start button and open the loading  
door. The cylinder should stop rotating within  
seven seconds after the door is opened a  
maximum of 2 inches (51 mm). If it does not,  
adjust the loading door switch. Refer to  
Adjustments section.  
WARNING  
Do not operate tumbler if airflow switch is  
faulty. An explosive gas mixture could  
collect in tumbler if airflow switch does not  
operate properly.  
W407  
7. Gas Tumblers: Start the tumbler and check the  
burner flame. Adjust the air inlet shutter as  
required. Refer to Adjustments section.  
10. Wipe out the cylinder using an all-purpose  
cleaner or detergent and water solution. Refer to  
IMPORTANT: The electronic ignition system will  
attempt to light the gas by sparking for the “trial  
for ignition” period. If gas does not ignite within  
this period, the ignition control will go into a safety  
lockout and the valve will no longer open until the  
control is reset. It may be necessary to retry several  
times to bleed air from the gas lines. To reset, open  
and close the loading door and restart tumbler.  
Reset  
Prepurge  
Time  
Trial for  
Ignition  
Lockout  
Condition  
By:  
(seconds) (seconds)  
18  
18  
5
Open loading  
door  
Australia  
CE  
10  
Press reset  
buttonbehind  
front access  
panel  
T452I  
Figure 10  
1 – 3  
10  
Open loading  
door  
All Others  
If the tumbler does not meet ANY of the listed  
requirements, remove tumbler from use. Refer to  
Removing Tumbler from Service section.  
If lockout condition persists, check that the manual  
gas shut-off valve is in the ON position and that the  
gas service is properly connected. If condition still  
persists, remove tumbler from service.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
24  
   
Installation  
Required for CE Models Only  
Installing CE Gas Drying Tumblers  
Once machine is installed, please be sure to complete  
the following items:  
WARNING  
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
• Close gas shut-off valve to gas tumbler  
before servicing.  
• Close steam valve to steam tumbler  
before servicing.  
• Never start the tumbler with any guards/  
panels removed.  
Review and verify machine operation with  
customer.  
Leave all literature and a signed Declaration of  
Conformity with customer.  
Review machine warranty information with  
customer.  
Apply warning sticker on front panel of machine,  
in language appropriate to country of sale  
(included in literature packet).  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
tumbler is properly grounded.  
W002  
General Information  
This information is to be used when installing gas  
tumblers in countries and/or on gases different than the  
machine’s factory configuration. Tumblers are  
supplied from the factory for operation on Natural Gas  
1000 Btu/cu ft. (8914 kcal/m3), or L.P. Gas 2500 Btu/  
cu ft. (22,250 kcal/m3),in the countries of GB/IE/PT/  
ES/IT/GR/LU/CH. To install machines in any other  
country, or on any other gas, requires some level of  
modification.  
Machines are built in two different configurations:  
Natural Gas – regulated/governor  
Liquefied Petroleum (L.P.) Gas – not regulated/  
no governor  
Machines configured for Natural Gas (regulator/  
governor) may be converted to L.P. Gas (not regulated/  
no governor) with block-open kit, Part No. M400763.  
Serial plates supplied from the factory are configured  
for GB/IE/PT/ES/IT/GR/LU/CH. These instructions  
pertain to the situations when the country of use or gas  
supply is different than that on the serial plate.  
Table 1 describes the different gases that are available  
in different CE countries, and how the machines need  
to be configured to operate with those gases. In the  
CE, there are Natural Gas configurations that do not  
allow for machine regulation and L.P. Gas  
configurations that must be regulated. For L.P. Gas,  
third family B/P at 50 mbar, order Regulated Natural  
Gas machines and convert according to Table 1.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
25  
     
Installation  
Burner  
Orifice  
Pressure,  
mbar  
Supply  
Group Pressure,  
mbar  
Burner  
Orifice  
Part No.  
Country  
Code  
Capacity/ Diameter,  
Gas Type  
Quantity  
Model  
mm  
Natural Gas  
L.P. Gas  
H
B/P  
E
20  
30  
8.9  
No Governor  
8.9  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
DK/NO/  
SE/FI/CZ/  
EE/LV/LT/  
SI/SK  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
20  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
LL  
B/P  
B/P  
L
25  
12.6  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
DE**  
L.P. Gas  
30  
No Governor  
28.5  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
50  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
25  
12.6  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
NL  
B/P  
E+  
+
30  
No Governor  
No Governor  
No Governor  
8.9  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
20/25  
28/37  
20  
050  
075  
3.0  
2.9  
2
3
M401017  
N/A  
BE/FR*  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
H
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
GB/IE/PT/  
ES/IT/GR/  
LU/CH  
+
28/37  
20  
No Governor  
8.9  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
H
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
AT**  
CY/IS/MT  
HU  
B/P  
B/P  
H
50  
28.5  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
L.P. Gas  
30  
No Governor  
8.9  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
25  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
B/P  
H
30  
No Governor  
8.9  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Natural Gas  
L.P. Gas  
20  
050  
075  
3.7  
3.6  
2
3
M401000  
M401014  
PL  
3P  
37  
No Governor  
050  
075  
2.1  
2.0  
2
3
M401003  
M400999  
Table 1  
Burner orifice information at 0-2000 feet (0-600 meters)  
altitude.  
*
For Natural Gas, Group E+ applications, convert using  
L.P. Gas model and replace burner orifice(s).  
N/A = Part no longer available.  
** For L.P. Gas, Group B/P with 50 mbar supply pressure,  
convert using Natural Gas model, M411334 regulator  
spring kit and burner orifice(s).  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
26  
 
Installation  
Basic Configuration  
1. Determine the necessary conversion operations  
to convert from the factory-supplied  
configuration to the desired configuration.  
2. Perform the conversions required so the machine  
is properly configured for the desired country and  
gas (refer to Specific Conversion Procedures  
section):  
SPECIFIED  
LOCAL INLET  
PRESSURE  
How to Convert Gas Valve from Regulated to  
Unregulated  
NOTE: Conversion from regulated to unregulated  
is only needed when regulated tumblers were  
ordered, but unregulated tumblers were needed.  
2
3
1
How to Change Burner Orifice Size  
How to Adjust Gas Valve Governor/Regulator  
3. If applicable, peel off the appropriate country  
sticker (included with machine) and apply it to  
the serial plate over the existing country  
information.  
T103K  
1
2
3
Gas Shut-Off Valve (Ahead of pressure tap)  
Pressure Tap  
Gas Shut-Off Valve (Shown in closed  
position)  
4. If applicable, peel off the appropriate conversion  
sticker (included with machine) and apply it to  
the serial plate over the “ADJUSTED FOR  
______ GAS: ______” information.  
Figure 11  
Specific Conversion Procedures  
5. Commission tumbler for use.  
How to Convert Gas Valve from Regulated to  
Unregulated  
WARNING  
When converting the tumbler to a  
NOTE: Conversion from regulated to unregulated  
is only needed when regulated tumblers were  
ordered, but unregulated tumblers were needed.  
different gas or pressure, first verify that  
the supply inlet pressure is equipped with  
a pressure regulator (located ahead of the  
tumbler) that will maintain the gas supply  
Johnson G96 Gas Valve:  
at the inlet pressure specified.  
a. Disconnect electrical power from tumbler.  
Close gas shut-off valve to tumbler. Refer to  
W430  
b. Follow instructions in Conversion Kit, Part  
No. M400763 (Johnson Part No. Y71AA-5C).  
NOTE: This kit does not contain any burner  
orifices.  
c. Replace burner orifice(s) as per Table 1.  
d. Commission tumbler for use.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
27  
     
Installation  
1
13  
12  
10  
2
11  
9
8
7
3
6
4
5
TMB1527N  
1
2
3
4
5
6
7
Burner  
8
Anti-Torque Ring  
Manifold Pipe  
Gas Valve  
9
Regulator Plate  
Gasket  
10  
11  
12  
13  
Spud Holder  
Pressure Tap  
Plate  
Burner Orifice  
Regulator Cap  
Spud Holder Nut  
Burner Tube Openings  
Figure 12  
3. Install the new, correct burner orifice(s). Refer to  
How to Change Burner Orifice Size  
Figure 13 and Table 1. Torque each to 9 – 10 Nm.  
1. Disconnect electrical power from tumbler. Close  
4. Reinstall spud holder assembly to gas valve,  
making certain burner orifice(s) are in line with  
burner tube opening. Refer to Figure 13.  
gas shut-off valve to tumbler. Refer to Figure 11.  
2. Remove spud holder.  
Johnson G96 Gas Valve – Unscrew spud holder  
nut near gas valve. Remove the burner orifice(s)  
from spud holder. Refer to Figure 12.  
5. Commission tumbler for use.  
NOTE: Blank burner orifices are Part No.  
M400995.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
28  
 
Installation  
How to Adjust Gas Valve Governor/Regulator  
1. Check gas burner orifice (manifold) pressure as  
1
follows. Refer to Figure 12.  
2. Remove screw plug from pressure tap.  
3. Connect a “U”-tube manometer (or similar  
pressure gauge) to the burner orifice (manifold)  
pressure tap.  
BURNER  
ORIFICE  
TMB2015N  
4. Start tumbler and note pressure once flame is  
burning. Remove regulator cap and adjust  
regulator screw until the burner orifice pressure  
per applicable table is achieved. Replace  
regulator cap. Refer to Figure 12.  
1
Size Stamped on Orifice  
Figure 13  
5. Commission tumbler for use.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
29  
 
 
Exhaust Requirements  
Venting  
WARNING  
WARNING  
A drying tumbler produces combustible  
lint. To reduce the risk of fire, the tumbler  
To reduce the risk of fire due to increased  
static pressure, we do not recommend  
installation of in-line secondary lint filters  
or lint collectors. If secondary systems  
are mandated, frequently clean the  
must be exhausted to the outdoors.  
W057  
To reduce the risk of fire and  
accumulation of combustible gases, DO  
NOT exhaust tumbler air into a window  
well, gas vent, chimney or enclosed,  
unventilated area such as an attic wall,  
ceiling, crawl space under a building, or  
system to assure safe operation.  
W749  
IMPORTANT: Installing in-line filters or lint  
collectors will cause increased static pressure.  
Failure to maintain the secondary lint system will  
decrease tumbler efficiency and may void machine  
warranty.  
concealed space of a building.  
W059  
Layout  
Whenever possible, install tumblers along an outside  
wall where duct length can be kept to a minimum, and  
make-up air can be easily accessed. Construction must  
not block the airflow at the rear of the tumbler. Doing  
so would prevent adequate air supply to the tumbler  
combustion chamber.  
For maximum efficiency and minimum lint  
accumulation, tumbler air must be exhausted to the  
outdoors by the shortest possible route.  
Proper sized exhaust ducts are essential for proper  
operation. All elbows should be sweep type. Exhaust  
ducts must be assembled so the interior surfaces are  
smooth, so the joints do not permit the accumulation  
of lint. DO NOT use plastic or thin foil ducts – rigid  
metal ducts are recommended. Use exhaust ducts  
made of sheet metal or other noncombustible material.  
DO NOT use sheet metal screws or fasteners on  
exhaust pipe joints which extend into the duct and  
catch lint. Use duct tape or pop-rivets on all seams and  
joints.  
Make-Up Air  
A tumbler is forced air exhausted and requires provisions  
for make-up air to replace air exhausted by tumbler.  
IMPORTANT: Do not obstruct flow of combustion  
and ventilation air.  
Required Make-Up Air Opening  
(to the outside) for Each Tumbler  
Verify that old ducts are thoroughly cleaned out before  
installing new tumbler(s).  
Model  
50 Pound  
75 Pound  
F75  
Opening  
2
2
144 in (928 cm )  
WARNING  
2
2
195 in (1258 cm )  
Improperly sized or assembled ductwork  
causes excess back pressure which  
results in slow drying, lint collecting in  
the duct, lint blowing back into the room,  
2
2
250 in (1613 cm )  
Make-up air openings with louvers will restrict  
airflow. The opening must be increased to compensate  
for area taken up by louvers.  
and increased fire hazard.  
W355  
Make-up air openings in rooms containing tumbler(s)  
and/or gas fired hot water heater or other gravity vented  
appliances must be increased sufficiently to prevent  
downdrafts in any of the vents when all tumblers are in  
operation. Do not locate gravity vented appliances  
between tumbler(s) and make-up air openings. If it is  
necessary to duct make-up air to tumbler(s), increase  
area of duct work by 25% to compensate for  
NOTE: Exhaust ducts must be constructed of sheet  
metal or other noncombustible material. Such  
ducts must be equivalent in strength and corrosion  
resistance to ducts made of galvanized sheet steel  
not less than 0.0195 inches (0.495 mm) thick.  
Where the exhaust duct pierces a combustible wall or  
ceiling, the opening must be sized per local codes. The  
space around the duct may be sealed with noncombustible  
restrictions in air movement.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
30  
       
Exhaust Requirements  
IMPORTANT: For best performance provide an  
individual exhaust duct for each tumbler. Do not  
install a hot water heater in a room containing  
tumblers. It is better to have the water heater in a  
separate room with a separate air inlet.  
With the tumbler in operation, airflow at any point  
in the duct should be at least 1200 feet per minute  
(366 m/min.) to ensure that lint remains airborne. If  
1200 feet per minute cannot be maintained,  
schedule monthly inspections and cleaning of the  
ductwork.  
Individual Venting  
Manifold Venting  
For maximum efficiency and performance, it is  
preferred to exhaust tumbler(s) individually to the  
outdoors.  
While it is preferable to exhaust tumblers individually  
to the outdoors, a main collector duct may be used if it  
is sized according to Figure 16 and Figure 17. This  
illustration indicates minimum diameters, and should  
be increased if the collector length exceeds 14 feet (4.3  
m) and two 90° elbows. The diameter of a round duct  
must be increased by 10% for each additional 20 feet  
(6.1 m). Cross sectional area of a rectangular or square  
duct must be increased 20% for each additional 20 feet  
(6.1 m). Refer to Table 3 and Table 4 tab to determine  
equivalent ducting sizing. The collector duct may be  
rectangular or square in cross section, as long as the  
area is not reduced. Provisions MUST be made for lint  
removal and cleaning of the collector duct.  
IMPORTANT: At no point may the cross sectional  
area of installed venting be less than the cross  
sectional area of the exhaust outlet of the tumbler.  
The exhaust duct must be designed so the static back  
pressure measured 12 inches (305 mm) from the  
exhaust outlet does not exceed the maximum  
allowable pressure specified on the installation sticker  
on the rear of the tumbler.  
NOTE: Static back pressure must be measured  
with the tumbler running.  
The vent collector system must be designed so the  
static back pressure measured 12 inches (305 mm)  
from the exhaust outlet does not exceed the maximum  
allowable pressure of 0.5 W.C.I. (1.3 mbar) as  
specified on the installation sticker on the rear of  
tumbler. Static back pressure must be measured with  
all tumblers vented into the collector operating.  
The maximum allowable length venting is 14 feet (4.3 m)  
and two 90° elbows or equivalent. If the equivalent  
length of a duct required for an installation exceeds the  
maximum allowable equivalent length, the diameter of  
a round duct must be increased by 10% for each  
additional 20 feet (6.1 m). Cross section area of a  
rectangular duct must be increased by 20% for each  
additional 20 feet (6.1 m). Refer to Table 2 to  
determine equivalent venting.  
NOTE: Never connect a tumbler duct at a 90°  
angle to the collector duct. Refer to Figure 14.  
Doing so will cause excessive back pressure,  
resulting in poor performance. Never connect two  
tumbler exhaust ducts directly across from each  
other at the point of entry to the collector duct.  
NOTE: The maximum length of a flexible metal  
duct must not exceed 7.87 ft. (2.4 m) as required to  
meet UL2158, clause 7.3.2A.  
Duct  
Equivalent Length of Rigid  
Straight Duct  
With the tumbler in operation, airflow at any point  
in the duct should be at least 1200 feet per minute  
(366 m/min.) to ensure that lint remains airborne. If  
1200 feet per minute cannot be maintained,  
schedule monthly inspections and cleaning of the  
ductwork.  
Diameter  
8 in. (203 mm) One 90° elbow = 9.3 ft. (2.83 m)  
10 in. (254 mm) One 90° elbow = 11.6 ft. (3.5 m)  
12 in. (305 mm) One 90° elbow = 14 ft. (4.3 m)  
14 in. (356 mm) One 90° elbow = 16 ft. (4.9 m)  
16 in. (406 mm) One 90° elbow = 18.7 ft. (5.7 m)  
18 in. (457 mm) One 90° elbow = 21 ft. (6.4 m)  
Equivalent Length (feet) = 1.17 x Duct Diameter (inches)  
Table 2  
Example: A 12 inch (305 mm) diameter duct’s  
equivalent length of 14 feet (4.3 m) of duct and two  
90° elbows is:  
Equivalent Length = 14 feet + (2) 90° elbows  
= 14 feet + 14 feet + 14 feet  
T438I  
= 42 feet (12.8 m)  
Figure 14  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
31  
       
Exhaust Requirements  
3
4
2
1
5
TMB2103N  
1
2
3
4
5
Removable strip of panel in framing wall to permit removal of tumbler from framing wall  
Partition or bulkhead  
Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)  
2 in. (51 mm) minimum clearance on both sides of duct  
Exhaust airflow – maximum length of duct: 14 ft. (4.3 m)  
Figure 15  
NOTE: Do not install wire mesh or screen in  
exhaust duct opening to avoid lint build-up or  
impacting proper discharge of air from tumblers.  
NOTE: Inside of duct must be smooth. Do not use  
sheet metal screws to join sections.  
Consult your local building code for regulations which  
may also apply.  
NOTE: Where exhaust duct pierces a combustible  
wall or ceiling, the opening must be sized per local  
codes.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
32  
 
Exhaust Requirements  
1
2
L
K
J
I
H
G
F
D
C
B
A
E
3
ONE MANIFOLD ASSEMBLY  
TMB2019N  
1
NOTE: Where the exhaust duct pierces a  
combustible wall or ceiling, the opening  
MUST be sized per local codes.  
2
3
Outlet duct diameter  
45° typical  
Figure 16  
50/75 Pound  
8 in. (203 mm) Duct  
8 in. (203 mm)  
F75  
Duct  
Station  
10 in. (254 mm) Duct  
10 in. (254 mm)  
15 in. (381 mm)  
18 in. (457 mm)  
21 in. (533 mm)  
24 in. (610 mm)  
26 in. (660 mm)  
28 in. (711 mm)  
30 in. (762 mm)  
32 in. (813 mm)  
33 in. (838 mm)  
35 in. (889 mm)  
36 in. (914 mm)  
A
B
C
D
E
F
G
H
I
12 in. (305 mm)  
15 in. (381 mm)  
17 in. (432 mm)  
19 in. (483 mm)  
21 in. (533 mm)  
23 in. (584 mm)  
25 in. (635 mm)  
26 in. (660 mm)  
27 in. (686 mm)  
29 in. (737 mm)  
30 in. (762 mm)  
J
K
L
Table 3  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
33  
 
   
Exhaust Requirements  
1
2
L
L
K
J
I
J
K
I
CONTINUE  
TO A  
CONTINUE  
TO A  
3
TWO MANIFOLD ASSEMBLIES  
TMB2018N  
1
NOTE: Where the exhaust duct pierces a  
combustible wall or ceiling, the opening  
MUST be sized per local codes.  
2
3
Outlet duct diameter  
45° typical  
Figure 17  
50/75 Pound  
8 in. (203 mm) Duct  
13 in. (330 mm)  
17 in. (432 mm)  
18 in. (457 mm)  
24 in. (610 mm)  
27 in. (686 mm)  
30 in. (762 mm)  
33 in. (838 mm)  
34 in. (864 mm)  
37 in. (940 mm)  
39 in. (991 mm)  
40 in. (1016 mm)  
42 in. (1067 mm)  
F75  
Duct  
Station  
10 in. (254 mm) Duct  
15 in. (381 mm)  
22 in. (559 mm)  
26 in. (660 mm)  
30 in. (762 mm)  
34 in. (864 mm)  
37 in. (940 mm)  
40 in. (1016 mm)  
43 in. (1092 mm)  
46 in. (1168 mm)  
47 in. (1194 mm)  
50 in. (1270 mm)  
51 in. (1295 mm)  
A
B
C
D
E
F
G
H
I
J
K
L
Table 4  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
34  
 
   
Gas Requirements  
Obtain specific gas service pipe size from the gas  
supplier. Refer to Table 5 for general pipe size.  
WARNING  
The following must be furnished and installed by the  
customer for the gas service line to each tumbler.  
Refer to Figure 18.  
To reduce the risk of fire or explosion, DO  
NOT CONNECT THE GAS LINE TO THE  
TUMBLER IF THE GAS SERVICE IS NOT  
THE SAME AS THAT SPECIFIED ON THE  
TUMBLER SERIAL PLATE! It will first be  
necessary to convert the gas burner  
orifice and gas valve. Appropriate  
Sediment traps  
Shut-off valves  
Supply pressure taps  
conversion kits are available.  
It is important that equal pressure be maintained at all  
tumbler gas connections. This can be done by  
installing a 1 inch (25.4 mm) pipe gas loop to maintain  
equal pressure at all gas connections. Refer to  
W060  
IMPORTANT: Any product revisions or conversions  
must be made by the Manufacturer’s Authorized  
Dealers, Distributors or local service personnel.  
IMPORTANT: The tumbler must be isolated from  
the gas supply piping system by closing its  
individual manual shut-off valve during any  
pressure testing of the gas supply piping system at  
test pressure equal to or less than 0.5 psig  
(3.45 kPa, 34.5 mbar).  
WARNING  
To reduce the risk of fire or explosion, if  
the tumbler is to be connected to  
Liquefied Petroleum (L.P.) gas, a vent to  
the outdoors must be provided in the  
room where the tumbler is installed.  
IMPORTANT: The tumbler and its manually  
operated appliance gas valve must be disconnected  
from the gas supply piping system during any  
pressure testing of that system at test pressures in  
excess of 0.5 psi (3.45 kPa, 34.5 mbar).  
W062  
NATURAL GAS line pressure must be maintained at  
6.5 water column inches (1.62 kPa), with no less than  
5 water column inches (1.24 kPa) and no more than  
10.5 water column inches (2.61 kPa), with all gas  
appliances running (tumblers, water heaters, space  
heaters, furnace, etc.). An in-line pressure regulator  
may be required if the line pressure exceeds 8 water  
column inches (2.0 kPa) with all gas appliances  
running.  
IMPORTANT: The installation must comply with  
local codes or, in the absence of local codes:  
with the latest edition of the “National Fuel  
Gas Code,” ANSI Z223.1/NFPA 54 in the  
U.S.A.,  
LIQUID PETROLEUM GAS (L.P.) line pressure must  
be maintained at 11 water column inches (2.74 kPa),  
with no less than 10 water column inches (2.49 kPa)  
and no more than 13 water column inches (3.23 kPa),  
with all gas appliances running (tumblers, water  
heaters, space heaters, furnace, etc.).  
with CAN/CSA-B149.1 or Natural Gas and  
Propane Installation Code in Canada,  
and Australian Gas Association/Australian  
L.P. Gas Association requirements in  
Australia.  
For converting NON-CE models from Natural Gas to  
L.P. Gas:  
50 Pound - M4379P3  
75 Pound - M4454P3  
F75 Pound - M4609P3  
CE GASES refers to Installing CE Gas Drying  
Tumblers section, the above data does not apply to the  
CE.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
35  
 
Gas Requirements  
Turn on gas and check all pipe connections (internal  
and external) for gas leaks with a non-corrosive leak  
detection fluid. Purge air in gas service line by  
operating the tumblers in the drying mode. If burner  
does not light and unit goes into lockout, open and  
close the door and restart. Repeat these steps until  
burner ignites. Use pipe compound, resistant to  
actions of L.P. gas, on all pipe threads.  
2
3
1
4
5
8
WARNING  
7
Check all pipe connections, internal and  
external, for gas leaks using a non-  
corrosive leak detection fluid. To reduce  
the risk of explosion or fire, DO NOT USE  
AN OPEN FLAME TO CHECK FOR GAS  
LEAKS! Gas connections should be  
6
TMB2007N  
1
Gas Line to Tumbler  
Shut-Off Valve  
2
3
4
5
6
7
8
Gas Supply Piping System  
Gas “T” Fitting  
checked twice a year for leakage.  
W635  
6 in. (152 mm) Minimum Gas Pipe  
Gas Pipe Cap  
Sediment Trap  
Suppply Pressure Tap  
Figure 18  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
36  
 
 
Gas Requirements  
Gas Supply Pipe Sizing and Looping  
1
3
2
12  
11  
9
10  
1
2
3
4
5
6
7
8
9
4
M
5
8
6
7
TMB2126N  
1
2
3
4
Gas furnace (120,000 Btu/hr.)  
7
8
Minimum Pipe Size is 0.5 in. (12.7 mm)  
25 ft. (7.6 m)  
Gas water heaters (400,000 Btu/hr. each)  
Gas space heaters (70,000 Btu/hr. each)  
Sediment traps, supply pressure taps and  
shut-off valves. Refer to Figure 18.  
1 in. (25.4 mm) gas pipe loop  
9
Main regulator  
10  
11  
12  
Gas meter  
Pressure regulator (if required)  
5
6
50 pound tumblers (120,000 Btu/hr each)  
75 pound tumblers (165,000 Btu/hr each)  
F75 pound tumblers (215,000 Btu/hr each)  
19 ft. (5.8 m)  
SAMPLE CALCULATIONS:  
Equivalent length = Total length of main gas supply pipe to the far end of the tumblers.  
= 25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe  
= 44 ft. (13.4 m) Total Gas Line  
Total Btu/hr.  
= The sum of the Btu/hr. of all 50 pound tumblers being fed by the main gas supply pipe.  
= 9 x 120,000  
= 1,080,000 Btu/hr.  
Using Table 5, the main supply pipe diameter should be 2 in. (51 mm).  
IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers  
connected to single gas service. Other gas using appliances should be connected upstream from loop.  
Figure 19  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
37  
 
   
Gas Requirements  
Gas Pipe Size Required for 1000 Btu Natural Gas — 0.64 Specific Gravity  
at 7 ± 1.5 inches (17.4 ± 4 mbar, 1.74 ± 0.37 kPa) Water Column Pressure  
Equivalent Length  
25 feet  
(7.63 m)  
50 feet  
75 feet  
100 feet  
125 feet  
150 feet  
(45.75 m)  
Gas  
Appliances  
Total Btu/hr  
(15.25 m)  
(22.88 m)  
(30.50 m)  
(38.13 m)  
Based on 0.3 in. Water Column Pressure Drop for Length Given  
Sizes shown in inches (mm)  
100,000  
120,000  
140,000  
160,000  
180,000  
200,000  
300,000  
400,000  
500,000  
600,000  
700,000  
800,000  
900,000  
1,000,000  
1,100,000  
1,200,000  
1,300,000  
1,400,000  
1,500,000  
1,600,000  
1,700,000  
1,800,000  
1,900,000  
2,000,000  
2,200,000  
2,400,000  
2,600,000  
2,800,000  
3,000,000  
0.75 (19.05)  
0.75 (19.05)  
0.75 (19.05)  
0.75 (19.05)  
1 (25.40)  
0.75 (19.05)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
1 (25.40)  
1 (25.40)  
1 (25.40)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
1.25 (31.75)  
1.25 (31.75)  
1.5 (38.10)  
1.5 (38.10)  
1.5 (38.10)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
2 (50.80)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
2.5 (63.50)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3 (76.20)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
4 (101.60)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
3.5 (88.90)  
For L.P. Gas, correct the total Btu/hr by multiplying it by 0.6. The answer is the equivalent Btu on the  
above chart.  
The installation must conform with local codes or, in the absence of local codes:  
with the latest edition of the “National Fuel Gas Code,” ANSI Z223.1/NFPA 54 in the U.S.A.,  
with CAN/CSA-B149.1 or Natural Gas and Propane Installation Code in Canada,  
and Australian Gas Association/Australian L.P. Gas Association requirements in Australia.  
Table 5  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
38  
 
 
Gas Requirements  
High Altitude Burner Orifice Sizing  
For proper operation at altitudes above 2000 feet  
(610 m), the gas burner orifice size must be reduced to  
ensure complete combustion. Refer to Table 6.  
For CE models, consult local gas supplier.  
Altitude  
Burner Orifice  
No. inches mm Quantity Part Number  
28 0.1405 3.6  
New Rate  
Model  
Gas  
feet  
meters  
(Btu/hr.)*  
110,400  
100,800  
91,200  
Natural Gas 2001-6000  
6001-8000  
610-1830  
2
3
3
M401014  
M400997  
M401021  
M401011  
M401027  
M401003  
M400999  
M400997  
M401021  
M401017  
M401027  
M401003  
M400999  
M401001  
M401020  
M402997  
M400998  
M400997  
M403017  
M406184  
M401011  
M401027  
1831-2440 29 0.1360 3.4  
8001-10,000 2441-3050 30 0.1285 3.3  
L.P. Gas  
2001-4000  
4001-6000  
6001-8000  
610-1220  
44 0.0860 2.2  
110,400  
100,800  
91,200  
50 Pound  
1221-1830 45 0.0820 2.1  
1831-2440 46 0.0810 2.1  
8001-10,000 2441-3050 47 0.0785 2.0  
81,600  
Natural Gas 2001-4000  
4001-8000  
610-1220  
29 0.1360 3.4  
151,800  
138,600  
125,400  
151,800  
138,600  
125,400  
112,200  
197,800  
180,600  
163,400  
146,200  
197,800  
180,600  
163,400  
146,200  
1221-2440 30 0.1285 3.3  
8001-10,000 2441-3050 31 0.1200 3.0  
L.P. Gas  
2001-4000  
4001-6000  
6001-8000  
610-1220  
45 0.0820 2.1  
75 Pound  
1221-1830 46 0.0810 2.1  
1831-2440 47 0.0785 2.0  
8001-10,000 2441-3050 48 0.0760 1.9  
Natural Gas 2001-4000  
4001-6000  
610-1220  
23 0.1540 3.9  
1221-1830 25 0.1495 3.8  
1831-2440 27 0.1440 3.7  
6001-8000  
8001-10,000 2441-3050 29 0.1360 3.4  
F75  
L.P. Gas  
2001-4000  
4001-6000  
6001-8000  
610-1220  
42 0.0935 2.4  
1221-1830 43 0.0890 2.3  
1831-2440 44 0.0860 2.2  
8001-10,000 2441-3050 45 0.0820 2.1  
* Btu/hr. derate of 4% per 1000 feet (305 meters) of altitude.  
Table 6  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
39  
 
   
Electrical Requirements  
This tumbler must be grounded. In the event of  
malfunction or breakdown, grounding will reduce the  
risk of electric shock by providing a path of least  
resistance for electric current. This tumbler must be  
connected to a grounded metal, permanent wiring  
system; or an equipment grounding conductor must be  
run with the circuit conductors and connected to the  
appropriate ground location.  
WARNING  
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
• Close gas shut-off valve to gas tumbler  
before servicing.  
Metal conduit and/or BX cable is not considered  
ground.  
• Close steam valve to steam tumbler  
before servicing.  
• Never start the tumbler with any guards/  
panels removed.  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
Connecting the Neutral from the electrical  
service box to the tumbler ground screw does not  
constitute a ground.  
A dedicated ground conduit (wire) must be  
connected between the electrical service box  
ground bar and tumbler ground screw.  
tumbler is properly grounded.  
W002  
WARNING  
To reduce the risk of electrical shock,  
de-energize the electrical circuit being  
connected to the tumbler before making  
any electrical connections. All electrical  
connections should be made by a  
qualified electrician. Never attempt to  
connect a live circuit.  
W409  
machine, if there is a “High Leg” or  
“Stinger Leg” it should be connected to  
CAUTION  
Label all wires prior to disconnection  
when servicing controls. Wiring errors  
can cause improper and dangerous  
operation. Verify proper operation after  
servicing.  
L3.  
W069  
Grounding Instructions  
W071  
NOTE: To ensure protection against shock, this  
tumbler MUST be electrically grounded in  
accordance with the local codes, or in the absence  
of local codes, with the latest edition of the National  
Electrical Code ANSI/NFPA No. 70. In Canada the  
electrical connections are to be made in accordance  
with CSA C22.1 latest edition Canadian Electrical  
Code, or local codes. Electrical work should be  
done by a qualified electrician.  
For CE Models Only  
All OPL (non-vend) models are factory-equipped with  
an emergency stop button on the front panel.  
NOTE: Activation of the emergency stop switch  
stops all machine control circuit functions, but  
DOES NOT remove all electrical power from  
machine.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
40  
     
Electrical Requirements  
Service/Ground Location  
Model  
Heat Source  
Ground and Terminal Block Locations  
Terminal  
Block  
E
F
U
E S  
S
U F  
E
F
U
E S  
S
U F  
Gas or Steam  
Non-CE  
L1  
T1  
L2 L3  
F
Z
Y
V
X
F
Z
Y
V
X
F
R
R
T
2
T
3
W
U
W
U
Ground  
Screw  
TMB1274N  
Junction Box  
Terminal  
Block  
Electric  
Non-CE  
Ground  
Lug  
TMB2124N  
Accessory Box  
NOTE: Do not make service connections in junction box.  
Power  
Disconnect  
Ground  
Screw  
Gas or Steam  
CE  
TMB1275N  
Power  
Disconnect  
Electric  
CE  
Ground  
Screw  
TMB2125N  
Figure 20  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
41  
 
Electrical Requirements  
To Connect Electrical Service To  
The Tumbler  
The following steps outline the procedure for  
connecting the electrical service to the tumbler.  
NOTE: The wiring diagram is located in the  
junction or contactor box.  
1. Install a circuit breaker as close to the tumbler as  
possible. If more than one tumbler is being  
installed, a disconnect switch or circuit breaker  
should be provided for each. This will make it  
possible to disconnect each tumbler for  
maintenance purposes.  
2. Connect the conduit-encased leads to the disconnect  
switch, or circuit breaker. Connect the wire leads  
to the appropriate labeled terminal on the terminal  
block. The ground wire must be connected to the  
ground connection as shown in Figure 21.  
3. Check the electrical service phase sequence  
(three phase only) as follows:  
a. Energize the electrical service (on reversing  
tumblers, ensure nonreversing is selected) and  
momentarily start the tumbler. Check the  
direction of the cylinder rotation. If the  
cylinder rotates clockwise (viewed from the  
front), the phase sequence is correct. If the  
cylinder rotates counterclockwise, proceed  
with step b.  
NOTE:When viewed from the front, the  
fan should rotate clockwise on 50 and 75  
Pound models and counterclockwise on  
F75 models.  
b. Disconnect and reverse any two service leads  
on the terminal block.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
42  
 
Electrical Requirements  
2
1
3
4
8
5
6
NON-CE MODELS  
T224S  
1, 2  
9
5
7
5
8
CE MODELS  
TMB2017N  
1
2
3
4
5
Electrical Service (Gas and Steam Models)  
Electrical Service (Electric Models)  
Accessory Box  
6
7
8
9
Ground Screw (Gas and Steam Models Only)  
Ground Buss Bar  
Contactor Box  
Ground Lug  
Disconnect Switch  
Fuses (Location may vary)  
Figure 21  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
43  
 
 
Electrical Requirements  
Jumper Configuration Instructions  
Ferrite Ring Installation  
Changing the transformer configuration jumper is  
required, PRIOR TO SUPPLYING POWER TO  
THE MACHINE, if any of the following apply:  
Gas and Steam OPL Control Models Only  
The ferrite ring provided in the literature packet must  
be installed over the power leads during connection of  
electrical service. The ferrite protects the sensitive  
electronic controls from destructive electrical  
disturbances which may be present on power lines to  
the machine. Failure to properly install the ferrite ring  
may result in damage to the electronic controls and  
will void control warranty.  
IMPORTANT: Failure to install the proper  
configuration jumper may result in damage to  
sensitive electronic controls and may void  
warranty.  
You have 200 – 208 Volt service and are  
connecting a model rated for 240 Volt operation.  
To install:  
Replace the 240 Volt jumper with the 208 Volt  
jumper per the conversion label, located on the  
rear of the tumbler, sign and date conversion  
label to document the conversion.  
1. Immediately after connection of power leads and  
before applying power to machine, locate each of  
the incoming service leads including ground.  
2. Snap the ferrite ring closed over all the service  
leads inside of the contactor box as shown. It is  
important that the ferrite ring be installed inside  
the contactor box. Refer to Figure 22. Do not  
install the ferrite outside of the box or other area.  
Make sure that service leads are in the center of  
the ferrite before closing the ring so as not to  
pinch or damage leads.  
You have 400 – 415 Volt service and are  
connecting a model rated for 380 Volt operation.  
NOTE: CE electro-mechanical timer models (MT,  
RT and CD control suffixes) do NOT require  
conversion jumper.  
Replace the 380 Volt jumper with the 415 Volt jumper  
per the conversion label, located on the rear of the  
tumbler, sign and date conversion label to document  
the conversion.  
1
2
3
T225S  
1
2
3
Ferrite Ring  
Contactor Box  
Jumper  
Figure 22  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
44  
 
     
Electrical Requirements  
NOTE: Electrical specifications below are subject  
to change without notice. Always refer to product  
serial plate for most current specifications of  
product being installed.  
50 Pound Gas and Steam Models  
Refer to Table 7.  
NOTE: Wire sizes were obtained from the  
Canadian Electrical Code for 75 C. wire and are  
intended for use as a guideline only. Electrical  
connections should be made by a qualified  
electrical contractor in accordance with all  
applicable local and national requirements.  
NOTE: Use copper conductors only.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
7
Serial Plate Amps  
Recommended Circuit  
Wire Size  
Terminal Block  
Connections  
Required  
Serial Plate Rating  
Nonreversing Reversing Breaker Rating  
2
AWG (mm )  
L1, Neutral and ground  
L1, Neutral and ground  
L1, L2 and ground  
9.3  
5.1  
5.1  
N/A  
N/A  
N/A  
15A – 1 pole  
10A – 1 pole  
10A – 2 pole  
14 (2.08)  
14 (2.08)  
14 (2.08)  
120V/60Hz/1ph  
200-208V/60Hz/1ph  
200-208-240V/60Hz/  
1ph  
L1, Neutral and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
6.3  
2.8  
3.3  
2.8  
3.1  
1.6  
1.6  
1.4  
1.4  
6.9  
4.0  
4.2  
4.0  
4.3  
2.0  
2.0  
1.9  
1.9  
15A – 1 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
230-240V/50Hz/1ph  
200-208V/60Hz/3ph  
200V/50Hz/3ph  
240V/60Hz/3ph  
230-240V/50Hz/3ph  
380V/50 or 60Hz/3ph  
400-415V/50Hz/3ph  
440V/60Hz/3ph  
460-480V/60Hz/3ph  
N/A = Not Applicable  
Table 7  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
45  
 
   
Electrical Requirements  
NOTE: Use copper conductors only.  
75 Pound Gas and Steam Models  
Refer to Table 8 and Table 9.  
NOTE: Connect to individual branch circuit.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
NOTE: Wire size and breaker ratings were  
obtained from the Canadian Electrical Code for  
75 C. wire and are intended for use as a guideline  
only. Electrical connections should be made by a  
qualified electrical contractor in accordance with  
all applicable local and national requirements.  
NOTE: Electrical specifications below are subject  
to change without notice. Always refer to product  
serial plate for most current specifications of  
product being installed.  
Serial Plate Amps  
Recommended Circuit  
Terminal Block  
Serial Plate Rating  
Connections  
Required  
Wire Size  
AWG (mm )  
12 (3.31)  
Breaker  
Rating  
Nonreversing  
13.8  
Reversing  
N/A  
2
L1, Neutral and ground  
L1, Neutral and ground  
L1, L2 and ground  
20A – 1 pole  
15A – 1 pole  
15A – 2 pole  
120V/60Hz/1ph  
7.6  
7.6  
N/A  
N/A  
14 (2.08)  
200-208V/60Hz/1ph  
14 (2.08)  
200-208-240V/60Hz/  
1ph  
L1, Neutral and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
6.7  
3.8  
3.5  
3.8  
3.5  
1.8  
1.8  
1.9  
1.9  
7.0  
4.3  
4.5  
4.3  
4.9  
2.1  
2.1  
2.1  
2.1  
15A – 1 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
10A – 3 pole  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
14 (2.08)  
230-240V/50Hz/1ph  
200-208V/60Hz/3ph  
200V/50Hz/3ph  
240V/60Hz/3ph  
230-240V/50Hz/3ph  
380V/50 or 60Hz/3ph  
400-415V/50Hz/3ph  
440V/60Hz/3ph  
460-480V/60Hz/3ph  
N/A = Not Applicable  
Table 8  
F75 Gas Models Only  
Serial Plate Rating  
Serial Plate Amps  
Recommended Circuit  
Terminal Block  
Connections  
Required  
Wire Size  
AWG (mm )  
Breaker  
Rating  
Nonreversing  
N/A  
Reversing  
6.3  
2
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
15A – 3 pole  
15A – 3 pole  
10A – 3 pole  
14 (2.08)  
200-208V/60Hz/3ph  
240V/60Hz/3ph  
N/A  
N/A  
6.3  
3.1  
14 (2.08)  
14 (2.08)  
460-480V/60Hz/3ph  
N/A = Not Applicable  
Table 9  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
46  
 
     
Electrical Requirements  
NOTE: Use copper conductors only.  
50 and 75 Pound Electric Models  
NOTE: Connect to individual branch circuit.  
Refer to Table 10.  
NOTE: 3 Phase Only – Each tumbler must be  
connected to its own individual branch circuit  
breaker, not fuses, to avoid the possibility of “single  
phasing” and causing premature failure of the  
motor(s).  
NOTE: Wire size and breaker ratings were  
obtained from the Canadian Electrical Code for  
75 C. wire and are intended for use as a guideline  
only. Electrical connections should be made by a  
qualified electrical contractor in accordance with  
all applicable local and national requirements.  
NOTE: Electrical specifications below are subject  
to change without notice. Always refer to product  
serial plate for most current specifications of  
product being installed.  
Serial Plate Amps  
Recommended Circuit  
Terminal Block  
Connections  
Required  
Serial Plate Rating  
Wire Size  
Breaker  
Rating  
Nonreversing  
Reversing  
2
AWG (mm )  
L1, Neutral and Ground  
93  
95  
125A – 1 pole  
1 (42.4)  
240V/50Hz/1ph  
(50 Pound only)  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
L1, L2, L3 and ground  
89  
84  
73  
79  
79  
47  
43  
41  
38  
88  
85  
75  
78  
78  
48  
44  
41  
38  
125A – 3 pole  
125A – 3 pole  
100A – 3 pole  
100A – 3 pole  
100A – 3 pole  
60A – 3 pole  
60A – 3 pole  
51A – 3 pole  
50A – 3 pole  
1 (42.4)  
1 (42.4)  
3 (26.7)  
3 (26.7)  
3 (26.7)  
6 (13.3)  
6 (13.3)  
6 (13.3)  
6 (13.3)  
200-208V/60Hz/3ph  
200V/50Hz/3ph  
230V/50Hz/3ph  
240V/50Hz/3ph  
240V/60Hz/3ph  
380V/50 or 60Hz/3ph  
400-415V/50Hz/3ph  
440V/60Hz/3ph  
480V/60Hz/3ph  
Table 10  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
47  
 
   
Steam Requirements  
NOTE: Machines require a constant 80 to 100 psig  
Install vacuum breaker (optional), bucket trap  
(5.62 to 7.03 kg/sq cm) steam service for optimum  
operation. The maximum allowable steam pressure  
for use with 60 Hertz or 50 Hertz tumblers is  
125 psig (8.6 bar). In no case may the pressure  
exceed the above value.  
with built-in strainer and check valve. For  
successful operation of tumbler, install trap  
18 inches (457 mm) below coil and as near to the  
tumbler as possible. Inspect trap carefully for  
inlet and outlet markings and install according to  
trap manufacturer's instructions. If steam is  
gravity returned to boiler, omit trap but install  
vacuum breaker and check valve in return line  
near tumbler. Gravity return requires entire return  
plumbing be below steam coil outlets.  
Obtain specific steam service pipe sizes from steam  
system supplier or a qualified steam fitter.  
Refer to Figure 23 for proper steam pipe  
configurations.  
Install union and shut-off valve in return line and  
make final pipe connections to return header.  
To prevent condensate draining from headers to  
tumbler, piping should have a minimum 12 inch  
(305 mm) rise above respective header. Do not  
make steam connection to header with a  
NOTE: To prevent water hammering, route return  
lines below outlets of steam coils.  
horizontal or downward facing tee or elbow.  
Whenever possible, horizontal runs of steam  
lines must drain, by gravity, to respective steam  
header. Water pockets, or an improperly drained  
steam header will provide wet steam, causing  
improper operation of tumbler. If pockets or  
improper drainage cannot be eliminated, install a  
bypass trap to drain condensate from the low  
point in the steam header to the return.  
In both steam supply and steam return line, it is  
recommended that each have a pipe union and  
shut-off valve. This will enable you to disconnect  
the steam connections and service the tumbler  
while your laundry facility is in operation.  
Connect the steam solenoid valve to the related  
steam coil inlet connection with nipples, flex  
hoses, unions and tees.  
Strainers may require cleaning due to materials  
from hoses or pipes.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
48  
 
Steam Requirements  
Piping Recommendations  
WARNING  
The flexible steam hoses connecting the  
coil outlet connections and steam traps  
must have a minimum of 125 psig  
(pounds per square inch gauge) (8.79 kg/  
sq. cm.) working pressure. A shut-off  
valve must be installed downstream from  
each steam trap so the condensate return  
line can be isolated in event a steam trap  
requires maintenance.  
Trap each steam coil individually. Always keep  
the trap clean and in good working condition.  
When tumbler is on the end of a line of  
equipment, extend header at least 4 feet (1.2 m)  
beyond tumbler. Install shut-off valve, union,  
check valve and bypass trap at end of line. If  
gravity return to boiler, omit trap.  
Insulate steam supply and return lines for safety  
of operator and safety while servicing tumbler.  
Keep tumbler in good working condition. Repair  
or replace any worn or defective parts.  
Each steam trap must be supported so  
minimum load is exerted on the coil outlet  
connection.  
W066  
WARNING  
Thermal Oil Prep  
All system components must have a  
125 psig (8.6 bar) working pressure.  
Shut-off valves must be installed upstream  
of the steam solenoid valve and  
downstream of each steam trap so  
components can be isolated for  
It is the responsibility of the customer to install  
appropriate coil and heating system for thermal oil  
prep models. Alliance Laundry Systems, LLC. is not  
responsible for the performance or safety of the  
customer installed thermal oil system. To ensure  
proper operation, refer to the Specifications and  
Dimensions section for the BTU input of equivalent  
steam models. Thermal oil systems that do not deliver  
appropriate BTUs will dry slower. For solenoid valve  
wiring connections, refer to the Wiring Diagram  
supplied with tumbler.  
maintenance or emergency purposes.  
All components (solenoid valve, traps)  
must be supported to minimize loads on  
the tumbler steam coil connections.  
W480R2  
Installing Steam Trap and Making  
Condensate Return Connections  
The steam trap must be installed and the coil outlet  
connections must be connected to the condensate  
return lines. The following steps outline the procedure  
for installing the steam trap and connecting the  
condensate return lines. Refer to Figure 23 for typical  
installations.  
1. Use flexible lines between steam inlet solenoid  
and steam coils, as well as outlet between steam  
coil and traps.  
2. If necessary, install a strainer at the end of each  
flexible hose.  
3. Install a steam trap to each strainer.  
IMPORTANT: Steam trap must be installed a  
minimum of 18 inches (457 mm) below the steam  
coil outlet connections.  
4. Install a shut-off valve to each steam trap.  
5. Connect to the condensate return lines.  
6. For steam solenoid valve wiring connections,  
refer to Wiring Diagram supplied with tumbler.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
49  
     
Steam Requirements  
2
1
11  
12  
6
3
4
13  
5
10  
9
8
7
6
TMB2014N  
NOTE: Refer to Table 11 for sizing of steam lines. Piping must also be sized accordingly for length of runs,  
and number of elbows.  
1
2
3
4
5
6
7
Supply  
8
9
18 in. (457 mm) Drop  
12 in. (305 mm) Riser  
Shut-Off Valve  
Solenoid Valve (Supplied with machine)  
10 Steam Bonnet  
11 Flexible Line  
Condensate Return Line from Supply Line  
Return  
12 Union  
Check Valve  
13 Trap with Built-In Strainer  
Vacuum Breaker (Optional)  
Figure 23  
Steam Trap Size*  
(Pounds Condensate/Hour)  
Steam Pressure PSI (bar)  
Minimum Pipe Diameter  
80 – 100 (5.3-6.9)  
3/4 in. NPT  
160  
*Based on 100 psi.  
Table 11  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
50  
 
     
Single Drop Timer  
NOTE: The following information is for  
models with an SD control suffix only.  
Setting Dry Time Dipswitches  
To change the dry time on the tumbler, combinations  
of dipswitches can be set on the control.  
Power-Up Mode  
There are eight dipswitches on the tumbler control.  
The first six switches are used to program the amount  
of additional heat time given for each coin pulse. The  
additional drying time is added to the factory default  
minimum heat time of one minute. A valve of 1 to 64  
minutes of additional drying time is available for each  
coin drop pulse.  
When power is applied to the tumbler, the IN USE  
light flashes factory status information. Following this,  
the control goes into READY Mode (light off) or RUN  
Mode if power was interrupted during a cycle (light  
on, time remaining unchanged).  
Ready Mode  
The last two switches are used to program the amount  
of additional cool down time. The additional cool  
down time is added to the factory default minimum  
cool down time of 1 minute. A value of 1 to 3  
additional minutes is available. The control is shipped  
from the factory programmed with 1 minute of  
minimum heat time, preset with 7 additional minutes  
of drying time (dipswitches 1, 2 and 3 in ON position)  
and 1 minute of minimum cool down time for a total  
time of 9 minutes for a coin pulse. For dipswitch  
settings Refer to Table 12.  
In READY Mode (light off), the control waits for the  
vend to be satisfied. When vend is satisfied the control  
goes into START Mode.  
Start Mode  
In START Mode (light on), the vend has been satisfied  
but the start button has not been pressed. Time  
remaining in the cycle will not change until the start  
button is pressed. When the start button is pressed the  
machine goes into RUN Mode.  
The control reads the dipswitch settings at power-up.  
The control must be powered down to change the  
dipswitch settings.  
Run Mode  
In RUN Mode (light on), the machine is running a  
cycle and the time remaining is counting down. When  
time remaining counts down to zero, the control goes  
into READY Mode.  
To change the time for a coin pulse, the desired dry  
time dipswitches must be set to ON position. All other  
dipswitches must be in OFF position.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
51  
           
Single Drop Timer  
Dipswitch Settings  
Cool Down  
Switch Number  
Heat Switch Number  
Cool Down Per  
Cycle (in Minutes)  
Heat Time Per Coin  
1
2
3
4
5
6
7
8
Pulse (in Minutes)  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
ON  
1
1 (factory default)  
2
2
3
4
OFF  
ON  
OFF  
ON  
3
ON  
ON  
4
OFF  
ON  
OFF  
OFF  
ON  
5
ON  
6
OFF  
ON  
ON  
7
ON  
ON  
8 (factory default)  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
9
ON  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
Table 12 (Continued)  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
52  
 
 
Single Drop Timer  
Table 12 (Continued)  
Heat Switch Number  
Heat Time Per  
Coin Pulse (in  
Minutes)  
1
2
3
4
5
6
ON  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
OFF  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
Total Cycle Time = Heat Time + Cool Down Time  
Table 12  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
53  
 
 
Rotary Coin Drop Timer  
NOTE: The following information is for models  
with a CD control suffix only.  
Removal of Existing Timing Cam  
1. Rotate cam by hand until “V” notch lines up  
beneath the ratchet tooth. Refer to Figure 24.  
Installing Accessory Timing Cam  
2. Insert narrow screwdriver under nylon cam, close  
to the clock shaft. Lift gently off shaft. Make sure  
that pressure is directed upward and that the “V”  
notch clears the ratchet tooth.  
Non-electronic, rotary coin drop tumblers have eight  
accessory cams in the literature package. These allow  
you to change your vending times. Refer to Table 13.  
Timer motor rpm is printed on the timer motor.  
Installation of New Timing Cam  
Vend Times (minutes)  
1. Insert drive fork into timing cam with wide prong  
in wide hole of cam.  
1/30 rpm Timer 1/60 rpm Timer  
Cam Pins  
Motor  
15  
Motor  
30  
2. Position timing cam and drive fork over the timer  
shaft, aligning the timer flat with the drive fork  
and the “V” notch with one of the ratchet teeth.  
2
3
10  
20  
7.5  
6
15  
4
3. Press timing cam down firmly to seat timing cam  
onto the motor shaft.  
12  
5
5
10  
6
3.75  
3
7.5  
6
8
10  
12  
2.5  
5
Table 13  
1
2
T039I  
1
2
Line Up Notch to Clear Ratchet Tooth  
Lift Gently with Narrow Blade  
Figure 24  
4. Remove all accumulated time by turning cam  
counterclockwise until switch shuts off. Apply  
moderate clockwise pressure to fully seated  
timing cam and drive against the timing motor  
shaft. Meter must be advanced electrically for  
one cycle before an accurate measure of time can  
be made.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
54  
 
           
Adjustments  
5. After air shutter is adjusted for proper flame,  
tighten air shutter adjusting screw securely.  
WARNING  
To reduce the risk of electric shock, fire,  
explosion, serious injury or death:  
• Disconnect electric power to the  
tumbler before servicing.  
PROPER AIRFLOW  
• Close gas shut-off valve to gas tumbler  
before servicing.  
• Close steam valve to steam tumbler  
before servicing.  
• Never start the tumbler with any guards/  
panels removed.  
• Whenever ground wires are removed  
during servicing, these ground wires  
must be reconnected to ensure that the  
1
tumbler is properly grounded.  
W002  
Gas Burner Air Shutter  
INSUFFICIENT AIRFLOW  
NOTE: Air inlet shutters on the burner must be  
adjusted so sufficient air is metered into the system  
for proper combustion and maximum efficiency.  
Before adjusting the inlet shutters be sure that all  
lint is removed from lint compartments and lint  
screen.  
Air shutter adjustments will vary from location to  
location and will depend on the vent system, number  
of units installed, make-up air and line gas pressure.  
Opening the shutter increases the amount of primary  
air supplied to the burner while closing the shutter  
decreases the primary air supply. Adjust air shutter as  
follows:  
1
Refer to Figure 25.  
NO AIRFLOW  
1. Open the access panel.  
2. Start the tumbler and check the flame pattern. If  
the flame pattern is straight up, insufficient air is  
flowing through the tumbler and airflow switch is  
improperly set. A flame pattern that flares to the  
right and left indicates no air is flowing through  
the tumbler. Correct air and gas mixture is  
indicated if the flame pattern is primarily blue,  
with small yellow tips, and bends to the right of  
the heater section. Too little air is indicated if the  
flame if yellow, lazy and smokey.  
1
T457I  
3. To adjust the air shutter, loosen air inlet shutter  
adjusting screw.  
T457I  
1
Air Shutter Adjusting Screws  
Figure 25  
4. Open or close air shutter as necessary to obtain  
proper flame intensity.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
55  
 
     
Adjustments  
The airflow switch operation is controlled by the  
counterweight position in the shaft. Moving the  
counterweight either increases or decreases airflow  
switch sensitivity. The counterweight should be  
adjusted so the disc moves away from the cabinet  
when the lint panel is opened 1.5 inches (38.1 mm) with  
a full load. Adjust the airflow switch as follows:  
Airflow Switch  
Gas and Electric Tumblers  
WARNING  
To reduce the risk of fire due to  
inadequate airflow, the airflow switch  
must be adjusted to operate per the  
instructions in this manual.  
1. Load the tumbler. This adjustment is much faster  
to make with one person opening lint panel in  
front and another adjusting the counterweight in  
the rear of tumbler.  
W674  
The airflow switch (located on the rear of tumbler,  
Figure 26) is set at the factory for proper operation.  
However, if there is a problem with the switch, it  
should be adjusted as follows:  
2. Temporarily tape down the lint panel safety  
switch located behind the upper right corner of  
the lint panel.  
3. Start the tumbler. Open the lint panel 1.5 inches  
(38.1 mm). The airflow disc should move away  
from the cabinet, opening the switch contacts and  
shutting off the heat system. This indicates  
proper operation and proper adjustment.  
Confirm exhaust duct and make-up air vents are  
properly sized and not obstructed. Refer to  
Make-Up Air and Venting sections.  
Confirm lint screen is clean and access panels are  
in place.  
4. If switch is not opening as described in step 3, it  
should be adjusted so it is MORE sensitive.  
Depress the spring clip and move counterweight  
toward disc. Retest by opening lint panel and  
continue moving counterweight toward disc until  
switch operates as described in step 3.  
Check operation of airflow switch and adjust as  
follows:  
NOTE: Steam models do not have an airflow  
switch.  
5. If switch opens BEFORE lint panel is opened the  
proper distance, step 3, it should be adjusted so it  
is LESS sensitive. Depress the spring clip and  
move counterweight away from the disc. Retest  
by opening lint panel and continue moving  
counterweight away from disc until switch  
operates as described in step 3.  
IMPORTANT: Remove tape from lint panel switch.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
56  
   
Adjustments  
2
4
3
1
5
10  
10  
6
6
9
8
7
9
8
7
T041I  
1
2
3
4
5
Airflow Switch  
6
Switch Lever  
Spring Clip  
Counterweight  
Disc  
Mounting Bracket  
Rear Panel of Tumbler  
Switch Mounting Screws  
Screw  
7
8
9
10  
Vane Lever Arm  
Figure 26  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
57  
 
 
Adjustments  
Loading Door Switch  
Drive Belt  
Loading door switch is factory preset, no field  
adjustment is necessary.  
Nonreversing Models  
Refer to Figure 28.  
Loading Door Catch  
Proper tension is when the drive V-belt can be  
depressed approximately 0.5 inch (13 mm) by  
applying light thumb pressure at a point midway  
between the sheave and motor pulley.  
The door catch must be adjusted to have sufficient  
tension to hold loading door closed against force of load  
tumbling against it. Proper adjustment is when 8 to  
15 pounds (35.6 N – 66.7 N) pull is required to open  
door.  
1. Remove guard from rear of tumbler.  
2. To adjust belt tension, loosen idler housing bolts  
holding idler housing assembly to the guide rails.  
If adjustment is required, refer to Figure 27 and  
proceed as follows:  
3. Position housing assembly by turning adjusting  
bolt until proper belt tension is reached, then  
retighten idler housing bolts.  
To adjust, open door, loosen acorn nut and turn door  
strike screw in or out as required. Tighten acorn nut.  
4. Replace the guard on rear of tumbler.  
Reversing Models  
Refer to Figure 29.  
Proper tension is when the drive belt can be depressed  
approximately 0.5 inch (13 mm) by applying light  
thumb pressure (approximately 5 pounds [0.35 bar]) at  
a point midway between the sheave and motor pulley.  
1
Proper tension is when each cylinder belt can be  
depressed approximately 0.19 inch (5 mm) by applying  
light thumb pressure (approximately 5 pounds  
[0.35 bar]) at a point midway between the sheave and  
the idler.  
1. Remove guard from rear of tumbler.  
2. To adjust cylinder belt tension, loosen idler  
housing bolts holding idler housing assembly to  
the guide rails.  
2
3. Position housing assembly by turning adjusting  
bolt until proper belt tension is reached, then  
retighten idler housing bolts.  
3
NOTE: Adjusting the cylinder belt tension will  
change the drive tension. Drive belt tension must  
also be adjusted.  
T048I  
4. Loosen the locking bolt.  
1
2
3
Door Latch  
Door Catch  
Acorn Nut  
5. Loosen the adjusting nut and use the adjusting  
screw to move the motor up or down.  
6. Once proper belt tension is reached, retighten the  
adjusting nut and locking bolt.  
Figure 27  
7. Replace the guard on rear of tumbler.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
 
58  
           
Adjustments  
1
2
3
5
4
NONREVERSING MODELS  
TMB816N  
1
2
3
Poly V-Belt (Self-Adjusting)  
Idler Housing Bolts (2)  
Adjusting Bolt  
4
5
Drive V-Belt  
Idler Housing Assembly  
Figure 28  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
59  
 
 
Adjustments  
1
8
7
2
3
6
4
5
REVERSING MODELS  
TMB817N  
1
2
3
4
Locking Bolt  
5
6
7
8
Guide Rail  
Adjusting Nut  
Adjusting Screw  
Cylinder Belts  
Idler Housing Bolts (2)  
Adjusting Bolt (Not shown)  
Drive Belt  
Figure 29  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
60  
 
 
Removing Tumbler from Service  
If the tumbler is to be removed from service, perform  
the following steps where applicable:  
Turn off electrical supply external to machine.  
Turn off electrical disconnect on machine.  
Turn off gas supply external to machine.  
Turn off manual gas shut-off valve on machine.  
Turn off steam supply external to machine.  
Remove all electric, gas and steam connections.  
M414905  
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT  
61  
 
 

ACP EP Memory Computer Drive CISURF MBM 1G User Manual
Air Oasis Air Cleaner Induct 9 User Manual
Alamo Lawn Mower DSEB D16 User Manual
Aleratec Computer Accessories 310108 User Manual
Alliance Laundry Systems Washer Accessories 802715 User Manual
AMX Computer Monitor i EquipmentMonitor User Manual
A T International Cordless Telephone CL82101 User Manual
Audiovox Remote Starter APS 510a User Manual
Baby Trend Baby Accessories 8181bt User Manual
Beko Refrigerator GNE60020X User Manual